Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual
Page 111
MS-9050 Series Manual — P/N 52413:G 4/14/2014
111
Master Programming Level
Programming
3+1, 4+1 Express, and 4+1 Standard
The information shown in Table 3.3 is automatically programmed for the Central Station phone
number Event Codes when any of these Formats are selected. Enter 0 for an Event Code Setting to
disable the report.
Event Description
Event Code Settings
Active
Restoral
PULL STATION
1
E
MON-USER-DEF-1
1
E
WATERFLOW
1
E
MON-USER-DEF-2
1
E
SMOKE (PHOTO)
1
E
DET-USER-DEF-1
1
E
SMOKE (ION)
1
E
DET-USER-DEF-2
1
E
HEAT DETECT
1
E
DET-USER-DEF-3
1
E
SMOKE DUCT-P
1
E
DET-USER-DEF-4
1
E
PHOTO W/HEAT
1
E
DET-USER-DEF-5
1
E
DUCT SUPERVISORY
8
E
DET-USER-DEF-6
8
E
PHOTO SUPERV
8
E
DET-USER-DEF-7
8
E
MONITOR
1
E
MON-USER-DEF-3
1
E
SMOKE CONVEN
1
E
MON-USER-DEF-5
1
E
HEAT CONVEN
1
E
MON-USER-DEF-6
1
E
MEDIC ALERT
0
0
MON-USER-DEF-7
0
0
HAZARD ALERT
0
0
MON-USER-DEF-8
0
0
TORNADO ALRT
0
0
MON-USER-DEF-9
0
0
TAMPER
8
E
MON-USER-DEF-11
8
E
MON SUPERVISORY
8
E
MON-USER-DEF-12
8
E
MON SUPERV AUTO
8
E
MON-USER-DEF-13
8
E
HVAC OVRRIDE
8
E
POWER MON
6
A
MON-USER-DEF-14
6
A
TROUBLE MON
POINT_FAULT code will always be transmitted
MON-USER-DEF-15
POINT_FAULT code will always be transmitted
PROCESS MON
0
0
MON-USER-DEF-16
0
0
PROCMON AR
0
0
MON-USER-DEF-17
0
0
Table 3.3 Event Codes