Module programming – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual
Page 66

66
MS-9050 Series Manual — P/N 52413:G 4/14/2014
Programming
Master Programming Level
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the 
first letter of the Description, Adjective or Noun field as follows:
•
If the zero key is pressed, a 0 is placed in the first letter position.
•
If the zero key is then pressed a second time with no intervening key actions, the entire field is 
replaced with the field entered for the previous device programmed, and the cursor moves to 
the last character of the field (Recall function). The Recalled Adjective or Noun field may 
now be changed letter-by-letter.
•
If the zero key is pressed again with no other intervening key actions and the last character in 
the field is a number 0-9, the number is incremented by one (9 will change to 0). If the last 
character is a letter, it changes to a 0.
•
The above increment function may be repeated with each press of the zero key.
As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows:
1.
The cursor is on the first letter of the Adjective field. Press the zero key twice to display 
FLR_3.
2.
With the cursor on the first letter of the Noun field, press the zero key twice to recall the dis-
play ROOM_304. The cursor automatically jumps from the first to the last letter of the Noun 
field.
3.
With the cursor on the last letter of the Noun field, press the zero key again to increment the 
room number to 305.
4.
Press the Enter key to store the information.
Module Programming
Pressing 2, while viewing Point Program Screen #2, will allow the programmer to add, delete or 
change the programming of an addressable module. The following screen will be displayed by the 
control panel: 
Add Module
Pressing 1 while viewing the Modules Screen will display the following screen which allows the 
programmer to add a new module address to programming: 
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in 
the three digit module address, such as 006. 
When the last digit is keyed-in, the following screen will be displayed:
POINT PROGRAM
SELECT TYPE
1=DETECTOR
2=MODULE
Point Program Screen #2
MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
ADD MODULE
ENTER MODULE#
QQQ
Add Module Screen #1
ADD MODULE
1=CONTROL
2=MONITOR
Add Module Screen #2