Programming
Master Programming Level
The Communication Format is determined by the type of receiver that the DACT is transmitting to.
Consult your Central Station for proper selection or consult our factory representatives. For any
format chosen, the control panel automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while viewing the
appropriate Comm Format screen. The following table describes each format:
Event Codes
Pressing 1 while viewing Primary/Secondary Screen #4 will cause the following screen to be dis-
played:
Pressing the down arrow key allows viewing of all Events associated with the selected Communi-
cation Format. Pressing the number corresponding to the event displayed in each screen will dis-
play its default event code which can be customized by the programmer. For example, pressing 1
for Pull Station will display the following screen which allows the Event Code to be changed from
the default value.
The tables on the following pages list all of the Events and their default Event Codes for the various
Communication Formats.
Screen Selection
Communication Format Description
ADEMCO EXPRESS 4P1
4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
ADEMCO EXPRESS 4P2
4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
3P1S C18 A23
3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3P1E C18 A23
3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
3P1S C19 A14
3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
3P1E C19 A14
3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
4P1S C18 A23
4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
4P1E C18 A23
4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4P1S C19 A14
4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
4P1E C19 A14
4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
4P2S C18 A23
4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
4P2E C18 A23
4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
4P2S C19 A14
4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
4P2E C19 A14
4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
ADEMCO CONTACT ID
Contact ID, DTMF, 1400/2300 ACK
Table 3.2 Communication Formats
CENTRAL STATION
1=EVENT CODES
Primary/Secondary Screen #4
EVENT CODES
1=PULL STATION
2=MON-USER-DEF-1
3=WATERFLOW
Event Code Screen
PULL STATION 115
Event Code Screen