Appendix d: facp with keltron – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual
Page 170
170
MS-9050 Series Manual — P/N 52413:G 4/14/2014
Appendix D: FACP with Keltron
The following figure illustrates the connections between the FACP and Keltron Receiver/Transmit-
ter.
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20
feet and enclosed within conduit or equivalently protected against mechanical injury.
!
CAUTION:
POSSIBLE EQUIPMENT DAMAGE
FOR REASONS OF WIRING DIAGRAM CLARITY, TERMINAL DESIGNATIONS OF KELTRON
MODULES ARE NOT SHOWN IN ACTUAL ORDER. FOLLOW KELTRON MANUAL AND MODULE
MARKINGS FOR EXACT TERMINAL LOCATIONS TO PREVENT SEVERE MODULE DAMAGE!
Fire Alarm Control Panel
(terminal blocks are not shown in their actual positions in
order to clarify wiring connections)
Keltron 95M3158 TTM-RPS
1.
Terminals 7 and 8: Remote station alarm/trouble inputs.
2.
Terminals 9 and 10: Sprinkler supervisory input.
Note: Cut TBL jumper on 4XTMF module to send
alarm/trouble signal from the same pair or terminals.
Alarm/Trouble Signal
Sprinkler
Supervisory
Signal
*Note: For more information,
refer to Keltron manual.
4XTMF Module
Figure D.1 FACP With Keltron Wiring