Master Programming Level
Programming
To change the Ring Count, press 1 while viewing the OnBoard DACT Screen #2. The following
screen will be displayed:
A flashing cursor will appear in the lower left corner of the display. Enter the two-digit ring count
which can be a value between 00 and 25. After the second digit is entered, the display will return to
the Service Terminal screen.
Central Station
Central Station programming configures the control panel DACT for contacting the central station.
Pressing 2 while viewing On Board DACT Screen #2 will cause the following screens to be dis-
played:
Note that the user will be prevented from entering the Central Station Options Screen while the
DACT is busy calling the Central Station.
Reporting Enable
To enable the DACT for reporting FACP activity to the central station, press 1 while viewing Cen-
tral Station Screen #1 so the display reads Reporting Enabled. Each press of the 1 key will toggle
the display between Reporting Disabled and Reporting Enabled.
Backup Reporting
The DACT can be programmed to transmit reports to primary and/or secondary central station
phone numbers as a backup. Press 2 while viewing Central Station Screen #1 to display the follow-
ing screen:
Press 1 to have all reports transmitted to the central station secondary phone number as a backup
only if the primary phone line fails, 2 to transmit all reports to both the primary and secondary
phone numbers all of the time, or 3 to send reports to the first available phone number.
Trouble Call Limit (Dialer Runaway Prevention)
The Call Limit option limits the number of DACT trouble calls to the Central Station, to a pro-
grammed amount between 0 and 99, for each unique trouble within a 24 hour period. All call limit
counters reset (clear) at each midnight. Separate limit counters keep track of each unique type of
trouble. Note that the number of phone number (communication) faults called to the Central Sta-
tion are not limited by this feature. No subsequent restoral message is sent to the Central Station(s)
for a particular trouble whose call limit has been reached. Local DACT annunciation will still track
the particular trouble and restoral.
RING COUNT
0-25 RANGE
Ring Count Screen
CENTRAL STATION
1=REPORTING DISABLED
2=REPORT BACKUP
3=CALL LIMIT 0
Central Station Screen #1
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Central Station Screen #2
BACKUP REPORTING
1=BACKUP ONLY
2=BOTH
3=FIRST AVAILABLE
Backup Reporting Screen