Installation
Notification Appliance Circuits
2.5 Notification Appliance Circuits
The control panel provides two NACs (Notification Appliance Circuits) Style Y (Class B) or Style 
Z (Class A). Each circuit is capable of 2.5 amps of current. Total current in alarm for all external 
devices cannot exceed 2.5 amps (refer to “Calculating the System Current Draw” on page 154).  
Use UL listed 24 VDC notification appliances only. Circuits are supervised and power-limited. 
Refer to the Fire-Lite Device Compatibility Document for a listing of compatible notification appli-
ances. The NACs, which are located on the main circuit board, may be expanded via the Fire-Lite 
FCPS Series field charger/power supplies.
NACs can also be configured for auxiliary power. If set for auxiliary power (door holder, resettable 
power, non-resettable power) do not connect notification appliances. Refer to Section 1.2, “Speci-
fications” for power capability.
The following sections describe the configuration and wiring of Style Y and Style Z Notification 
Appliance Circuits on the FACP main circuit board. 
2.5.1 Configuring NACs
The Notification Appliance Circuits are configured for Style Y (Class B) or Style Z (Class A) by 
properly wiring the NAC devices to TB1 on the main circuit board as illustrated below.
TB1
B+
B-
B-
B+
A+ A-
A+ A-
NAC1
NAC2
-
+
B
+
B
-
1
4
A
+
A
-
2 3
+
+
B
+
B
-
A
+
A
-
+
+
+
5 6 7 8
Figure 2.6 NAC Wiring
Style Y (Class B) Notification Appliance 
Circuits, supervised and power-limited - 
4.7 K
, ½ watt P/N:71252 UL listed
Polarized Bells
Polarized Horns
Polarized Horns
Polarized Strobes
Notification Appliance Circuit 
polarity shown in alarm state
Dummy Load all unused 
circuits with a 4.7 K
, ½ watt
resistor across the B+ & B- 
terminals or wire jumpers 
between A+ & B+ and A- & B-.
90
50
ud
n
a
c
.wmf
Polarized Strobes
terminal number
NAC 1
NAC 2
Style Z (Class A) Notification Appliance 
Circuits, supervised and power-limited
Polarized Bells