Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual
Page 67
MS-9050 Series Manual — P/N 52413:G 4/14/2014
67
Master Programming Level
Programming
Pressing 1 for Control Module or 2 for Monitor Module will cause the following screen to be dis-
played:
The programmer can continue adding modules by pressing the ESC or left arrow key which will
return the display to the Add Module Screen #1.
Delete Module
Pressing 2 in the Modules Screen will display the Delete Module Screen which allows the pro-
grammer to delete a specific module:
A flashing cursor will appear in the position of the first asterisk to the left. Using the panel keypad,
key in the module address such as 006. When the last digit is keyed in, the following confirmation
that the module has been deleted will be displayed:
Edit Module Screen for Monitor Module
The programmer can change a modules existing or factory default programming by pressing 3 in
the Modules Screen. The following screen will be displayed:
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit module address, such as 012.
When the last digit is keyed-in, if the selected address has not been added to programming, a screen
showing information about a device that is installed with a lower address, closest to the selected
address, will be displayed. If no modules are installed on the loop, the following screen will be dis-
played:
If the selected address has been added to programming but a module (such as a monitor module)
with the selected address is not physically installed on the SLC or has a communication fault, the
following screen will be displayed:
ADD MODULE
MODULE# 006
IS ADDED
Add Module Screen #3
MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
DELETE MODULE
ENTER MODULE#
QQQ
Delete Module Screen
DELETE MODULE
MODULE# 006
IS DELETED
EDIT MODULE
ENTER MODULE ADDRESS
QQQ
Edit Module Screen
NO MODULE
INSTALLED
Edit Module Screen
TROUBL MONITOR
ZNNN
Q 1M012