Programming
Master Programming Level
ANN-LED Options Screen
Pressing 2 for Module Options while viewing ANN-BUS Address Screen when the ANN-LED
option is selected, will display the following screen:
The first screen indicates that the ANN-LED at the selected ANN-BUS address is programmed to
annunciate Alarms, Troubles and Supervisories for Zones 00 through 09. The programming can be
changed using ANN-LED Address Screen 2.
Pressing 1 while viewing ANN-LED Address Screen #2 will program the annunciator module to
annunciate either Point (addressable device address) information or Zone information. Each press
of the 1 key will toggle the display between Point and Zone.
Pressing 2 while viewing ANN-LED Address Screen #2 will program the annunciator module to
annunciate only Alarms or Alarms, Troubles and Supervisories (ATS). Each press of the 2 key will
toggle the display between Alarms and ATS.
Pressing 3 while viewing ANN-LED Address Screen #2 will select the Point or Zone range to be
annunciated (refer to the tables in “ANN-RLED Zone Option - Alarm Only” on page 100 and
“ANN-RLED Point Option - Alarm Only” on page 101). Pressing the 3 key will display an addi-
tional screen where the range can be selected.
•
If Zone has been selected, and Alarms Only are to be annunciated, the 3 key will have no effect
since all zones can be displayed on only one ANN-LED module.
•
If Zone has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the
new screen will give the options of annunciating Zone 0 - 9 or 10 - 19. Two ANN-LED
modules are required to annunciate all zones in this configuration.
•
If Points has been selected, and Alarms Only are to be annunciated, the new screen will give
the options of annunciating Points 1 - 30 and 31 - 50. Two ANN-LED modules are required to
annunciate all points in this configuration.
•
If Point has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the
new screens will give the options of annunciating Points 1 - 10, 11 - 20, 21 - 30, 31 - 40 or 41 -
50. Five ANN-LED modules are required to annunciate all points in this configuration.
ANN-RLED Zone Option - Alarm Only
If Zone is selected as the module option, and the module is programmed to annunciate alarms only,
the first ten LEDs on the ANN-RLED module will display the system status information. The next
20 LEDs on the module will display the active/alarm status of each zone. The last 10 LEDs are not
used. The LED assignments for the ANN-RLED module will be as follows.
ANN-RLED Module
Alarm Silenced
NAC 1 Fault
NAC 2 Fault
Not Used
Not Used
Earth Fault
Battery Fault
Charger Fault
Disabled
Maintenance
Zone 00
Active/Alarm
Zone 01
Active/Alarm
Zone 02
Active/Alarm
Zone 03
Active/Alarm
Zone 04
Active/Alarm
Zone 05
Active/Alarm
Zone 06
Active/Alarm
Zone 07
Active/Alarm
Zone 08
Active/Alarm
Zone 09
Active/Alarm
Zone 10
Active/Alarm
Zone 11
Active/Alarm
Zone 12
Active/Alarm
Zone 13
Active/Alarm
Zone 14
Active/Alarm
Zone 15
Active/Alarm
Zone 16
Active/Alarm
Zone 17
Active/Alarm
Zone 18
Active Alarm
Zone 19
Active/Alarm
Not Used
Not Used
Not Used
Not Used
Not Used
PROGRAMMING
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
ANN-BUS Screen #3
ANN-LED ADDR #
ZONES 00-09
ALARM, TRBL, SUPV
ANN-LED Address Screen #1
ANN-LED ADDR #
1=POINT/ZONE ZONE
2=ALARM/ATS ATS
3=RANGE ZN00-09
ANN-LED Address Screen #2