UL Power-limited Wiring Requirements
Installation
2.6 UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-lim-
ited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through dif-
ferent knockouts and/or conduits. If installing an optional ANN-LC, ensure that the ground for the
AC mains is installed first, closest to the backbox. A typical wiring diagram for the FACP is shown
below.