Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual
Page 69
MS-9050 Series Manual — P/N 52413:G 4/14/2014
69
Master Programming Level
Programming
types and responses. To select the type of monitor module being programmed, press the 2 key
while viewing the Edit Monitor Screen #2. This will cause the control panel to display the first
Monitor Type Screen as illustrated below
To view additional Monitor Type Screens, press the down arrow key. While viewing one of the
Monitor Type screens, select the type of monitor module being programmed by pressing the corre-
sponding keypad number key. The display will return to the Edit Monitor Screen #2 which will
show the new type selection. The following table lists all of the Monitor Types available for pro-
gramming and their respective functions.
Monitor module type selection will affect the function of the point as follows:
Monitor Type
Action When Activated
Pull-Station
Fire Alarm
User-Defined-1
Fire Alarm
Waterflow
Fire Alarm Delayed (uses waterflow delay)
User-Defined-2
Fire Alarm Delayed (uses waterflow delay)
Monitor
Fire Alarm
User-Defined-3
Fire Alarm
Future Use
Future Use
Future Use
Future Use
Smoke-Conventional
1, 2
Fire Alarm
User-Defined-5
Fire Alarm
Heat-Conventional
Fire Alarm
User-Defined-6
Fire Alarm
Medic-Alert
3
Piezo, latching
User-Defined-7
Piezo, latching
Hazard-Alert
Piezo, latching
User-Defined-8
Piezo, latching
Tornado-Alert
Piezo, latching
User-Defined-9
Piezo, latching
Future Use
Future Use
Future Use
Future Use
Tamper
Supervisory, nonlatching (tracking)
User-Defined-11
Supervisory, nonlatching (tracking)
Supervisory
Supervisory, latching
User-Defined-12
Supervisory, latching
Supervisory-AR
4
Supervisory, nonlatching (tracking)
User-Defined-13
Supervisory, nonlatching (tracking)
HVAC OVRRIDE
5
Switch Supervisory, nonlatching (tracking)
Power-Monitor
AC Fault
User-Defined-14
AC Fault
Trouble-Monitor
Trouble
User-Defined-15
Trouble
Proc-Mon
Piezo
User-Defined-16
Piezo
Procmon-AR
Piezo, nonlatching (tracking)
User-Defined-17
Piezo, nonlatching (tracking)
Future Use
Future Use
Future Use
Future Use
Ack-Switch
Acts like panel Acknowledge Key
Sil-Switch
Acts like panel Alarm Silence Key
Reset-Switch
Acts like panel Reset Key
Table 3.1 Monitor Types
MONITOR TYPE
1=PULL-STATION
2=USER-DEFINED-1
3=WATERFLOW
Monitor Type Screen #1