Wire Requirements
NAC Wiring
E.1 NAC Wiring
The following table lists NAC wiring requirements for the FACP.
Calculations are based on Direct-Current Resistance data for uncoated copper wire, per National
Electrical Code (2005 Edition) Table 8, Conductor Properties.
NAC Load
(Amps)
Max.
allowable
total loop
resistance
(ohms)
CLASS-B
Max. allowable wire pair lenth
(feet)
CLASS-A
Max. allowable wire pair length
(feet)
AWG 12
solid
AWG 14
solid
AWG 16
solid
AWG 18
solid
AWG 12
solid
AWG 14
solid
AWG 16
solid
AWG 18
solid
0.25
13.20
3420
2150
1350
849
1710
1075
675
425
0.5
6.60
1710
1075
675
425
855
537
337
212
0.75
4.40
1140
717
450
283
570
358
225
142
1
3.30
855
537
337
212
427
269
169
106
1.25
2.64
684
430
270
170
342
215
135
85
1.5
2.20
570
358
225
142
285
179
112
71
1.75
1.89
489
307
193
121
244
154
96
61
2
1.65
427
269
169
106
214
134
84
53
2.25
1.47
380
239
150
94
190
119
75
47
2.5
1.32
342
215
135
85
171
107
67
42
Table E.2 NAC Wiring Requirements for FACP