Page 59
MS-9050 Series Manual — P/N 52413:G 4/14/2014
59
Master Programming Level
Programming
When Autoprogram is selected, the control panel will begin autoprogramming the system by com-
municating with each addressable device installed on the SLC loop. While autoprogramming, the
panel will display the following:
When Autoprogramming is completed, the control panel will display the type and quantity of each
device installed on the SLC loop similar to the following display:
In the preceding example, the display indicates that the SLC Loop has 22 addressable detectors, 15
monitor modules and 10 control modules installed.
Pressing the ESC key will return the display to Programming Screen #1.
3.6.2 Point Program
The Point Program option allows the programmer to add a new addressable device to an SLC loop,
delete an existing device from a loop or change the programming for an existing device. Pressing
2, while viewing Programming Screen #1, will select the Point Program option and display the fol-
lowing screen:
Detector Programming
Pressing 1, while viewing the Point Program Screen, will allow the programmer to add, delete or
change the programming of an addressable detector. The following screen will be displayed by the
control panel:
Add Detector
Pressing 1 while viewing the Detector Screen will display the following screen which allows the
programmer to add a new detector address to programming:
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit detector address, such as 005.
AUTOPROGRAM
AUTOPROGRAMMING!
PLEASE WAIT
Autoprogram Progress Screen
# OF DET LOOP1 022
# OF MON LOOP1 015
# OF CON LOOP1 010
Autoprogram Result Screen #1
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
POINT PROGRAM
SELECT TYPE
1=DETECTOR
2=MODULE
Point Program Screen
DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
ADD DETECTOR
ENTER DETECTOR#
QQQ
Add Detector Screen