Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual
Page 115
MS-9050 Series Manual — P/N 52413:G 4/14/2014
115
Master Programming Level
Programming
Ademco Contact ID Format
The information shown in Table 3.5 is automatically programmed for the Central Station phone
number Event Codes when Ademco Contact ID Format is selected. Enter 000 for an Event Code
Setting to disable the report.
Event Description
Event Code Settings
4+2
Active
Zone
Point
Restoral
Active
PULL STATION
115
Zone
Point
E1
11
MON-USER-DEF-1
115
Zone
Point
E1
11
WATERFLOW
113
Zone
Point
E1
11
MON-USER-DEF-2
113
Zone
Point
E1
11
SMOKE (PHOTO)
111
Zone
Point
E1
11
DET-USER-DEF-1
111
Zone
Point
E1
11
SMOKE (ION)
111
Zone
Point
11
11
DET-USER-DEF-2
111
Zone
Point
11
11
HEAT DETECT
114
Zone
Point
11
11
DET-USER-DEF-3
114
Zone
Point
11
11
SMOKE DUCT-P
116
Zone
Point
11
11
DET-USER-DEF-4
116
Zone
Point
11
11
PHOTO W/HEAT
111
Zone
Point
11
11
DET-USER-DEF-5
111
Zone
Point
11
11
DUCT SUPERVISORY
200
Zone
Point
11
81
DET-USER-DEF-6
200
Zone
Point
11
11
PHOTO SUPERV
200
Zone
Point
11
81
DET-USER-DEF-7
200
Zone
Point
11
11
MONITOR
110
Zone
Point
11
11
MON-USER-DEF-3
110
Zone
Point
11
11
SMOKE CONVEN
111
Zone
Point
81
11
MON-USER-DEF-5
111
Zone
Point
11
11
HEAT CONVEN
114
Zone
Point
81
11
MON-USER-DEF-6
114
Zone
Point
11
11
MEDIC ALERT
100
Zone
Point
11
0
MON-USER-DEF-7
100
Zone
Point
11
0
HAZARD ALERT
150
Zone
Point
11
0
MON-USER-DEF-8
150
Zone
Point
11
0
TORNADO ALRT
150
Zone
Point
11
0
MON-USER-DEF-9
150
Zone
Point
11
0
TAMPER
144
Zone
Point
0
81
MON-USER-DEF-11
144
Zone
Point
0
81
MON SUPERVISORY
200
Zone
Point
0
81
MON-USER-DEF-12
200
Zone
Point
0
81
MON SUPERV AUTO
200
Zone
Point
0
81
MON-USER-DEF-13
200
Zone
Point
0
81
HVAC OVRRIDE
200
Zone
Point
81
81
POWER MON
330
Zone
Point
81
81
MON-USER-DEF-14
330
Zone
Point
81
81
TROUBLE MON
POINT_FAULT code will always be transmitted
81
MON-USER-DEF-15
POINT_FAULT code will always be transmitted
81
PROCESS MON
000
81
0
MON-USER-DEF-16
000
81
0
PROCMON AR
000
81
0
Table 3.5 Event Codes