Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual
Page 146
146
MS-9050 Series Manual — P/N 52413:G 4/14/2014
Central Station Communications
The control panel is capable of reporting detailed messages depending upon the format in use.
Table 5.1 shows the reporting structure for all formats.
Refer to Table 5.2 for an explanation of each letter code in Table 5.1. Refer to Table 5.3 for a list of
compatible receivers.
Format Format Format
Format
Report
3+1/4+1/Standard
4+1 Express
3+1/4+1/Expanded
4+2/Standard
4+2 Express
4+2/Expanded
Alarm
SSS(S) A
SSS(S) A
AAA(A) Z
SSSS AA2
SSSS AZ
Alarm Restore
SSS(S) RA
SSS(S) RA
RARARA(RA) Z
SSSS RARA2
SSSS RAZ
Zone Trouble
(Zone Open)
SSS(S) TZ
SSS(S) TZ
TZTZTZ(TZ) Z
SSSS TZTZ2
SSSS TZZ
Zone Trouble Restore
SSS(S) RTZ
SSS(S) RTZ
RTZRTZRTZ(RTZ) Z
SSSS RTZRTZ2
SSSS RTZZ
System Trouble
SSS(S) TS
SSS(S) TS
TSTSTS(TS) Y
SSSS TSTS2
SSSS TSY
System Trouble Restore
SSS(S) RTS
SSS(S) RTS
RTSRTSRTS(RTS) Y
SSSS RTSRTS2
SSSS RTSY
Zone Disable
SSS(S) DZ
SSS(S) DZ
DZDZDZ(DZ) Z
SSSS DZDZ2
SSSS DZZ
Zone Disable Restore
SSS(S) RDZ
SSS(S) RDZ
RDZRDZRDZ(RDZ) Z
SSSS RDZRDZ2
SSSS RDZZ
Low Battery
SSS(S) L
SSS(S) L
LLL(L) L2
SSSS LL2
SSSS LL2
Low Battery Restore
SSS(S) RL
SSS(S) RL
RLRLRL(RL) RL2
SSSS RLRL2
SSSS RLRL2
AC Loss
SSS(S) P
SSS(S) P
PPP(P) P2
SSSS PP2
SSSS PP2
AC Loss Restore
SSS(S) RP
SSS(S) RP
RPRPRP(RP) RP2
SSSS RPRP2
SSSS RPRP2
Fire Drill
SSS(S) FD
SSS(S) FD
FDFDFD(FD) FD2
SSSS FDFD2
SSSS FDFD2
Fire Drill Restore
SSS(S) RFD
SSS(S) RFD
RFDRFDRFD(RFD) RFD2
SSSS RFDRFD2
SSSS RFDRFD2
Supervisory Condition
SSS(S) V
SSS(S) V
VVV(V) Z
SSSS VV2
SSSS VZ
Supervisory Condition
Restore
SSS(S) RV
SSS(S) RV
RVRVRV(RV) Z
SSSS RVRV2
SSSS RVZ
Test Report
SSS(S) X
SSS(S) X
SSSS XX2
SSSS XX2
Upload or Download
SSS(S) UD
SSS(S) UD
SSS UDUD2
SSS UDUD2
Table 5.1 Format Selection