Ann-led board layout and connection to facp, 7 ann-rly relay module, Specifications – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual
Page 50: Ann-rly relay module
50
MS-9050 Series Manual — P/N 52413:G 4/14/2014
Installation
ANN-BUS Devices
ANN-LED Board Layout and Connection to FACP
Figure 2.22 illustrates the ANN-LED board showing locations of screw terminals for connection to
the FACP and the DIP switches for selecting the ANN-BUS ID number.
2.9.7 ANN-RLY Relay Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a compat-
ible FACP.
Specifications
•
Operating Voltage: 24 VDC
•
Max. Current:
Alarm: 75 mA
Standby: 15 mA
•
Operating Temperature: 32
o
F to 120
o
F (0
o
C to 49
o
C)
•
For indoor use in a dry location only
Figure 2.22 ANN-LED Connection to FACP
ANN-LED
+24 VDC
-24 VDC
ANN-BUS and power wiring are
supervised and power-limited
MS-9050UD
Primary ANN-BUS
Ground wire from mounting screw to
FACP Earth Ground stud is required
for some Canadian applications.
(Refer to “ANN-LED Annunciator
Installation for Canadian
Applications” on page 181).
ANN-BUS (ID#)