2 ann-sec option card, Ann-sec option card – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual
Page 35
MS-9050 Series Manual — P/N 52413:G 4/14/2014
35
Optional Modules/Accessories Installation
Installation
8.
When the installation has been completed, enable the 4XTMF module by sliding the
disconnect switch to the left.
9.
Test system for proper operation.
2.8.2 ANN-SEC Option Card
The ANN-SEC option card allows for a secondary ANN-BUS. Install the ANN-SEC as follows.
1.
Remove the chassis mounting screw to the right of TB7 and replace it with the supplied 0.5” x
4-40 male-female standoff.
2.
Install the header into J13 on the main circuit board.
Figure 2.11 4XTMF Connectors to MS-9050UD Connectors
J8 & J9 Connectors
Jumper JP2
Standoff
Standoff
4XTMF
MS-9050UD
90
50
u
d
4
x
tm
.w
mf
Jumper JP28
NOTE: Jumper JP2 on the FACP main circuit board can be used to configure the FACP
supervisory relay for operation with the 4XTMF module. Relay 3 at TB3 must be programmed as
a supervisory relay.
Removing the jumper from JP2 will allow the 4XTMF to generate a trouble if the supervisory
contact opens
Leaving the jumper on JP2 will prevent generation of a trouble if the supervisory contact opens