REMOTE ANNUNCIATOR, MODEL RA400Z

Connect the remote annunciator between terminals 1 and 3 using the spade lug terminal included. The spade lug termi-
nal is connected to the base terminal as shown in Figure 5.

It is not acceptable for three stripped wires to be under the same wiring terminal unless they are separated by a washer
or a lug like the spade lug supplied with the model RA400Z. See Figure 5 for installation.

A78-1473-00

Figure 5. Connection to Remote Annunciator Terminal.

B310LP PLUG-IN DETECTOR BASE

INSTALLATION INSTRUCTIONS

Before installing detectors, please thoroughly read the system wiring and installation manuals, and manual I56-407,
Guide for Proper Use of System Smoke Detectors, which provides detailed information on detector spacing, placement,
zoning, and special applications. Copies of these manuals are available from Fire•Lite.

GENERAL DESCRIPTION

The B310LP Plug-in Detector Base is used with Fire•Lite models CP350 ionization, SD350 and SD350T photoelectronic de-
tectors, and H350 and H350R heat detectors

The B310LP base is intended for use in a 2-wire addressable system, with screw terminals provided for power (+ and –),
and remote annunciator connections. Communication takes place over the power (+ and –) lines.

BASE TERMINALS

NO.

FUNCTION

1

Power (–), Remote Annunciator (–)

2

Power (+)

3

Remote Annunciator (+)

A78-1318-00

STRIPPED WIRE

WIRE WITH
SPADE LUG

F400-21-00

1

I56-954-01R

Fire•Lite Alarms, Inc., One Fire•Lite Place, Northford, CT 06472, 203-484-7161

F400-21-00

4

I56-954-01R

©2000 Fire•Lite

Figure 1. Terminal Layout

SPECIFICATIONS

Diameter:

6.1 inches (155 mm)

Mounting:

4 inch (102 mm) square box with or without plaster ring
Min. Depth: 1.5 inches (38 mm)
4 inch Octagon Box, Min. Depth – 1.5 inches (38 mm)
3-1/2 inch Octagon Box, Min. Depth – 1.5 inches (38 mm)
Single Gang Box, Min. Depth – 1.5 inches (38 mm)

3

2

1

BASE
TERMINALS

TAMPER PROOF

TAB

Please refer to insert for the Limitations of Fire Alarm Systems