Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual
Page 74
74
MS-9050 Series Manual — P/N 52413:G 4/14/2014
Programming
Master Programming Level
1M002 - represents the Loop, Device type and Device address (1 = SLC Loop, M=Module,
and 002 = Module Address 02).
To change the programming for the displayed module, press the keyboard down arrow key to view
the following Edit Control screens:
Enable/Disable Module
To Enable or Disable the control module, press the 1 key while viewing the Edit Control Screen #2.
Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No
is selected, the module will not be polled by the control panel, preventing the module from activat-
ing its output devices. The control panel will indicate a system trouble condition and the Disable
LED will turn on if any devices are disabled.
Type
To select the type of control module being programmed, press the 2 key while viewing the Edit
Control Screen #2. This will cause the control panel to display the following Control Type Screens:
While viewing one of the Control Type screens, select the type of control module being pro-
grammed by pressing the corresponding keypad number key. The display will return to the Edit
Control Screen #2 and indicate the new type selection.
The following table contains control module type codes and their functions which are displayed in
the Control Type screens:
EDIT CONTROL
1=ENABLED YES
2=TYPE CONTROL
3=SILENCEABLE YES
Edit Control Screen #2
EDIT CONTROL
1=WALKTEST YES
2=ZONE ASSIGNMENT
00 QQ QQ QQ QQ
Edit Control Screen #3
EDIT CONTROL
1=ADJECTIVE/NOUN
2=DESCRIPTION
QQQQQQQQQQQQQQQQQQQQ
Edit Control Screen #4
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
CONTROL TYPE
1=BLANK
2=BELL-CIRCUIT
3=HORN-CIRCUIT
Control Type Screen #1
NOTE: A control relay module set to the Resettable Power type will follow the main circuit board
24 VDC resettable power unless the control relay module is disabled.
Control Type
Special Function
Blank
NAC Type - Supervised
Bell Circuit
NAC Type - Supervised
Horn Circuit
NAC Type - Supervised
Sounders
NAC Type - Supervised
Relay
Relay Type - Ignore Open Circuit
Strobe Circuit
NAC Type - Supervised
Control
NAC Type - Supervised
Resettable Power
1
1 When using a control relay module to supply resettable power to
conventional 2-wire smoke detectors, the addressable monitor module
must be programmed for “Smoke Conventional” operation.
Relay Type - Ignore Open Circuit
HVAC SHUTDN
2
2 For the HVAC SHUTDN description, refer to Section F.1, “Control
Module Operation”, on page 173.
Relay Type - Ignore Open Circuit