MS-9050 Series Manual — P/N 52413:G 4/14/2014
Programming
Master Programming Level
Hub Mode Setup
Pressing 2 while viewing the Lite-Connect Setup Screen will allow the programmer to configure
the MS-9050UD as the Lite-Connect hub FACP. The following screen is displayed.
Pressing 1 while viewing the Hub Mode Setup Screen will allow the programmer to enable the
MS-9050UD as the hub of the Lite-Connect circuit. One MS-9050UD FACP must act as a hub in
every Lite-Connect circuit. Select Enabled Yes if the current MS-9050UD will serve as the hub.
Each press of the 1 key will toggle the display between Enabled No and Enabled Yes.
Pressing 2 while viewing the Hub Mode Setup Screen will allow the programmer to edit the nodes
on the Lite-Connect circuit. The following screen is displayed. There is an edit node screen for
every available node on the Lite-Connect circuit (02-17). Scroll left or right to view the appropriate
node number.
Pressing 1 while viewing the Edit Node ## Screen will allow the programmer to enable an FACP as
a specific node on the Lite-Connect circuit. Each press of the 1 key will toggle the display between
Enabled No and Enabled Yes.
Pressing 2 while viewing the Edit Node ## Screen will allow the programmer to specify which type
of FACP will participate as a specific node on the Lite-Connect circuit. The following screen is
displayed.
Press 1 if the selected node is an MS-9050UD FACP.
Press 2 if the selected node is an MS-9200UDLS FACP.
Pressing 3 while viewing the Edit Node ## Screen will allow the programmer to specify alternate
account codes to be used to communicate that node’s events to the Central Stations. If these values
are left blank/zero the hub’s account codes will be used to report the event. The following screen is
displayed.
Press 1 or 2 to edit the central station account codes. The following screen displays for both
selections.
HUB MODE SETUP
1=ENABLED NO
2=EDIT NODES
Hub Mode Setup Screen
EDIT NODES ##
1=ENABLED YES
2=TYPE 50PT
3=ACCOUNT CODES
Edit Node ## Screen
NODE TYPE
1=50 POINTS
2=198 POINTS
Node Type Screen
EDIT NODES ##
1=ENABLED YES
2=TYPE 50PT
3=ACCOUNT CODES
Edit Nodes ## Screen
ACCOUNT CODES
1=CENTRAL STATION 1
2=CENTRAL STATION 2
CS1= CS2=
Node Type Screen
CENTRAL STATION X
ACCOUNT CODE
4 CHAR RANGE 0-F
Node Type Screen