beautypg.com

Fire-Lite 411UDAC Fire Alarm Communicator Relay User Manual

Fire-Lite Equipment

background image

Document #51128 Rev. A1 10/31/03 P/N 51128:A1

1 of 1

Installation:
The Fire Alarm Communicator provides sockets for two
Form-C relays (P/N:411RK) rated for 2.0 amps @ 30 VDC
(resistive). Relay 1 must be installed in the main circuit
board socket labeled K6 and Relay 2 must be installed in the
socket labeled K5.

1.

As a safety precaution, it is highly recommended that all power be removed from the main circuit board before
installing the optional relays

2.

Position the relay module so that the largest gap between the first set of pins and the second set is to the left as
illustrated in Figure 1

3.

Carefully align the relay module pins with the socket holes, making certain that the two pins on each end of
the relay line up with the two holes at each end of the socket

4.

Press the relay firmly into place, being careful not to bend any of the pins

Programming:
The relays are programmable for activation on fire alarm, host panel trouble, fire supervisory, process monitoring,
total communication failure, DACT trouble and security alarm. Refer to “DACT Programming” in the Fire Alarm
Communicator manual. Addresses ‘85 - 88’ are used for programming relay functions and enable.

Relay Module

Relay

Socket

Relay Module

41

1UDAB2

.CDR

Figure 1: Relay Installation

large gap

1st pins

RELAY 1

RELAY 2

TB1

NO

NO

NC

NC

C

C

Figure 2: Programmable Relay

Note: Relay connections may be power-limited or nonpower-limited, provided that 0.25" spacing is
maintained between conductors of power-limited and nonpower-limited circuits.

Relays automatically change to energized condition
when programmed for Trouble.

41

1A

RE

LE.C

D

R

Relay 1 - Shown Programmed for Alarm, Super-
visory, or any other function except DACT
Trouble, Host Panel Trouble and Process Moni-
toring
(relay contacts shown in deenergized condition
with power applied to Fire Alarm Communica-
tor)

Relay 2 - Shown Programmed for DACT
Trouble, Host Panel Trouble or Process Mon-
itoring (relay contacts shown in energized
condition with power applied to Fire Alarm
Communicator)

Document #51128 Rev. A1 10/31/03 ECN 03-742

Fire Alarm Communicator

Relay

Product Installation Drawing