ANN-BUS Devices
2.9.2 ANN-BUS Device Addressing
Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the
FACP. A 5-position DIP switch on each device is used to set this address. The address set for these
devices must also be programmed at the FACP for the specific device (refer to the programming
section titled “ANN-BUS” on page 96).
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that
00 is not a valid address. The following table shows the DIP switch setting for each address.
When installed and enabled through FACP programming, the ANN-LC will always be set to
address 08. No dip switch settings are used to set the address on the ANN-LC.
2.9.3 ANN-80(C) Remote Fire Annunciator/Indicator
The ANN-80(C) Annunciator/Indicator is a compact, 80 character, backlit LCD remote fire annun-
ciator which mimics the FACP display. It also provides system status indicators for AC Power,
Alarm, Trouble, Supervisory and Alarm Silenced conditions. The ANN-80 Annunciator provides a
button for Reset, Silence, Acknowledge, and Drill. The ANN-80C does not provide these buttons.
Communication between the ANN-80(C) and FACP is accomplished over a two wire serial inter-
face employing the ANN-BUS communication format. The devices are powered, via two addi-
tional wires, from either the host FACP or remote UL-listed, filtered, power supply.
Specifications
•
Operating Voltage Range: 18 VDC to 28 VDC
•
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal/Standby (no activity): 37.0 mA
Trouble: 39.0 mA
Alarm: 40.0 mA
AC Fail ( not backlit): 15.0 mA
•
For use indoors in a dry location
NOTE: Address (ID Number) DIP switches on some devices may have more than 5 switch
positions. Unless otherwise specified in the documentation supplied with each device, switch
positions 6 and above must be set to OFF.
Address
Switch 5
1
1 Switch 5 must be set to OFF for ANN-BUS devices to be recognized.
Switch 4
Switch 3
Switch 2
Switch 1
not valid
OFF
OFF
OFF
OFF
OFF
01
OFF
OFF
OFF
OFF
ON
02
OFF
OFF
OFF
ON
OFF
03
OFF
OFF
OFF
ON
ON
04
OFF
OFF
ON
OFF
OFF
05
OFF
OFF
ON
OFF
ON
06
OFF
OFF
ON
ON
OFF
07
OFF
OFF
ON
ON
ON
08
OFF
ON
OFF
OFF
OFF