beautypg.com

Aquametrix SHARK-120/240 Controllers User Manual User Manual

Page 130

background image

S

H

A

R

K

MULTI-PARAMETER CONTROLLER & ANALYZER USER’S MANUAL

Flow - Outputs Menu - 4-20mA CH2 Output 7.19

Flow - Outputs Menu - 4-20mA CH2 Output 7.19

Page 128

DOWN

DOWN

DOWN

DOWN

DOWN

DOWN

DOWN

DOWN

DOWN

DOWN

DOWN

DOWN

DOWN

DOWN

The Controller has 2 4-20mA outputs, electrically isolated from
each other and ground. Either output can source current into a
maximum of 800 ohms.
Channel 2 has fully independent and fully adjustable 4 & 20
mA output adjustments. This will enable the operator to span
the output over the desired range.

UP

NOTE

PRESS THE AND KEYS

TOGETHER TO GO IMMEDIATELY BACK TO

RUN MODE

DOWN

With "N" selected, pressing the
key will NOT store the selection, but
simply return to the OUTPUTS Menu.
This function is useful if you wish to
view the current selection without

Not stored

The TUNE function allows the user to
precisely adjust the 4-20mA output to
compensate for any errors in the
output circuitry. Normally, fine tuning
the 4-20mA output is not necessary.
The make the adjustment, place an
accurate current meter in series with
the 4-20mA output, with the
appropriate loads connected. When
the TUNE menu is selected, the
controller puts 20mA out to the
terminals. Use the or
keys to adjust the 20mA output to get
exactly 20.
The TUNE value can be adjusted
over the range from 0 to 1000, these
are unitless numbers used for tuning
purposes only.

UP

DOWN

DOWN

Then press the key to store the
selection and return to the OUTPUTS menu

DOWN

Or press the
key to highlight
the Y character

Stored

If you wish to change the setting, press the
key once which will move the cursor to the first
character of the value to be changed

The 4mA, 20mA and TUNE functions are set
up the same way as 4 - 20 mA CH 1 output.

RUN MODE

STORE? Y N

STORE? Y N

4-20mA CH2

20MA OUT 100.0 >

4MA OUT 0.00 >

4-20 CH2 PROC

20MA TUNE 512 >

4-20 CH2 PROC

4-20 CH2 PROC

4-20mA CH2 PROC

4-20mA CH2 PROC

4-20mA CH1

RELAY A

RELAY B

ALARM RELAY

CALIBRATION

DIAGNOSTICS

UTILITIES

OUTPUTS

SETUP

TOTAL 0