AquaMetrix pH and ORP differential

probes stay in service and provide accu-

rate measurements under conditions that

often render conventional pH probes in-

operable. Now for added versatility, these

probes, field-proven in hundreds of instal-

lations, are available with an integral en-

capsulated 4-20 mA two-wire transmitter

to feed directly to a PLC or a DCS.
The P65 pH and R65 ORP probes em-

ploy a differential measurement tech-

nique. Unlike conventional combination

probes, the differential probe has two

high impedance measurement circuits

containing a common metallic return

electrode. One circuit includes the pro-

cess measurement electrode which gen-

erates a potential E1 proportional to the

process pH. The second circuit includes

an internal measurement electrode im-

mersed in a stable buffer solution which

generates a standard reference potential,

E2. Both circuitshave a common potential

E3 developed at the return electrode. The

two circuits are fed into amplifiers which

provide an output representing the differ-

ential between them:
(E1 - E 3) - (E2 - E3). The common po-

tential E3 is cancelled out electronically,

greatly reducing inaccuracies caused by

ground loops which may exist between

process and instrument grounds. Ground

loop current willflow through the low im-

pedance path of the return electrode, af-

fecting the potential E3, but not the dif-

ferential measurement.

The differential probe maintains its accu-

racy and stability in aggressive process

applications long after a combination-

style probe’s performance begins to de-

teriorate.
Maintenance costs are reduced and the

life of the probe is increased. The internal

reference electrode is electrically con-

nected to the process solution by means

of a field-replaceable double junction salt

bridge which greatly reduces the possibil-

ity of contamination of the buffer solution

in the reference circuit. Although seldom

required, the reference solution may be

easily replaced by removing the screw-

out salt bridge. A salt bridge and buffer kit

is available for this purpose.
Another advantage of the 65 series is the

semi-flush face which is easily cleaned

and avoids solution materials gather-

ing on protrusions found in competitive

probes. The domed glass electrode, the

protective metal electrode and the tem-

perature sensor protrude only about 1/8

inch while the salt bridge is flush. A flat-

face version of the pH probe is also avail-

able.
The 65 series can be provided in any of

the physical configurations in the P60/

R60 series differential probes: 65C-8

with 1-1/2” threaded body style, 65C-6

“Easy-In, Easy-Out” variable insertion

depth version with 1- 1/4” NPT compres-

sion fitting, or the 65C-7 hot tap version.

Two-Wire Transmitter built in

Integral two-wire 4-20

mA transmitter can be fed

directly to PLC, DCS
Differential Measurement

Replaceable Salt Bridge

Long-lasting

Low Maintenance Cost

Field-proven

Reduces ground loop problems

Easy Cleaning

• Semi-flush face: re-

duced buildup
Temperature Compensation

Automatic temperature compen-

sation on pH versions
Options

Flow-through and submersion

Hot-Tap available

Flat-faced available (pH)

Gold electrode available (ORP)

Differential pH & ORP ver-

sions without 2 wire transmitter

available (see P/R60 series)

Aquametrix Model P65C/R65C

Probes with 4 to 20 mA Output

by

Water Analytics

AquaMetrix

100 School Street

Andover, MA 01810

978-749-9949

Toll free - 855-747-7623

www.WaterAnalytics.net

Process Control

Industrial and Municipal Wa-

ter Treatment

Industrial and Municipal

Waste Treatment and Neutral-

ization

Fume Scrubbers, Plating,

Circuit Board Manufacturing,

Food and Beverage, Chemi-

cal Processing, Pulp and Pa-

per, Mining, Power Generation,

Pharmaceutical Industry

Description

Features

Applications

by

Water Analytics

AquaMetrix

This manual is related to the following products: