Wiring for Power to Detector Heater

This wiring provides electric power from the converter to the heater for heating the
sensor in the detector.

CAUTION

Refer to section 3.1.

Detector

Converter

(1) Terminal box's surface temperature of the detector: 80

Њ

C or less

(2) Terminal box's surface temperature of the detector: exceeding 80

Њ

C

Heat-resistant wiring

HTR 7

HTR 8

HTR 7

HTR 8

HEATER

HEATER

Terminal box

F5.6E.EPS

Detector

Converter

Non-hazardous area

Non-hazardous area

Hazardous area

Hazardous area

Figure 5.6 Wiring for power to the detector heater

5.3.1

Cable Specifications

Basically, PVC insulated PVC sheathed control cables (2 cores) are used for this wiring.
When the ambient temperature of the detector exceeds 80

Њ C, install a terminal box, and

connect to the detector using six 600V silicon rubber insulated glass braided wires.

5.3.2

Connection to Detector

When connecting the cable to the detector, proceed as follows:

(1) Mount cable glands or conduits of the specified thread size to the wiring connections

of the detector.
The detector may need to be removed in future for maintenance, so be sure to allow
sufficient cable length.

(2) If the ambient temperature at the location of wire installation is 80 to 150

Њ C, be sure

to use a flexible metallic conduit for the wire. If a non-shielded “ 600V silicon
rubber insulated glass braided wire” is used, keep the wire away from noise sources
to avoid noise interference.