Chapter 11: Factory Page

To go to the Factory Page, press both the Up ¿ and Down ¯ keys for six seconds from the Home Page. {FAct} will
appear in the upper display and

{page} in the lower display.

• Press

the

Advance

Key

‰ to move through the parameter prompts.

• Press the Up ¿ or Down ¯ keys to change the parameter value.

• Press the Infinity Key ˆ at any time to return to the Home Page.

Display

Parameter Name

Description

Settings

Range

(Integer values for Modbus

in parentheses.)

Default

Modbus*

(less 40,001

offset)

Read/Write

Appears if:

[AMb]
[AMb]

Ambient Temperature
Displays the current calculated
ambient temperature.

-50.0 to 300.0°F

NA

Always active.

[A;mn]
[A.Mn]

Minimum Recorded Ambient
Temperature
Displays the minimum recorded
ambient temperature.

-50.0 to 300.0°F

NA

NA

Always active.

[AMa]
[A.MA]

Maximum Recorded Ambient
Temperature
Displays the maximum recorded
ambient temperature.

-50.0 to 300.0°F

NA

NA

Always active.

[dSPL]
[dSPL]

Display Intensity
Increase or decrease the bright-
ness of the upper and lower
display.

15 to 100% duty

100

NA

Always active.

[rESt]
[rESt]

Restore Factory Calibration
Replaces the user calibration pa-
rameters with the factory calibra-
tion parameters.

[~~no] (0)
[~yES] (1)

[~~no] (0)

208 R/W

Always active.

[USr;r]
[Usr.r]

Restore User Settings
Restores customer configured set-
tings. Two sets of user settings
for non-profiling version and one
set of user settings for profiling
version.

[~~no] (0)
[Set1] (1)
[Set2] (2)

[~~no] (0)
[~yES] (1)

[~~no] (0)

209 R/W

Non-profiling version
only.
(SD_ C - _ _ _ _ - _ _
_ _ )

Profiling version only.
(SD_ R - _ _ _ _ - _ _
_ _ )

[USr;S]
[USr.S]

Save User Settings
Saves customer configured set-
tings. Two sets of user settings
for non-profiling version and one
set of user settings for profiling
version.

[~~no] (0)
[Set1] (1)
[Set2] (2)

[~~no] (0)
[~yES] (1)

[~~no] (0)

210 R/W

Non-profiling version
only.
(SD_ C - _ _ _ _ - _ _
_ _ )

Profiling version only.
(SD_ R - _ _ _ _ - _ _
_ _ )

[PrF;r]
[PrF.r]

Restore User Profiles
Restores the current customer
configured profiles

[~~no] (0)
[~yES] (1)

[~~no] (0)

209 R/W

Profiling version only.
(SD_ R - _ _ _ _ - _ _
_ _ )

[PrF;S]
[Prf.S]

Save User Profiles
Saves the current customer con-
figured profiles.

[~~no] (0)
[~yES] (1)

[~~no] (0)

210 R/W

Profiling version only.
(SD_ R - _ _ _ _ - _ _
_ _ ).

[dFLt]
[dFLt]

Default Parameters
Reset all parameters to the de-
fault values (may take up to 4
seconds to complete).

[~~no] (0)
[~yES] (1)

[~~no] (0)

207 R/W

Always active.