Watlow Series SD PID Profiling Controller User Manual
Page 52
Wa t l o w S e r i e s S D
•
5 0
•
C h a p t e r 1 0 P r o f i l i n g
Display
Parameter name
Description
Set-
tings
Range
(Integer values for Mod-
bus in parentheses.)
Default
Modbus*
(less 40,001
offset)
Read/Write
Appears if:
[``JL]
Jump Loop Step
[``JF]
[ JF]
Jump File
Selects the file which is to be
jumped to. This is a zero-time step.
1 to 4
1
See page 53.
Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
[``JS]
[ JS]
Jump Step
Selects the step which is to be
jumped to. This is a zero-time step.
1 to 10
1
See page 53.
Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
[``JC]
[ JC]
Jump Count
Indicates the number of times the
jump is to be done. A value of 0 re-
sults in an infinite loop.
0 to 9999
1
See page 53.
Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
[LFiL] Link File Step
[``LF]
[ LF]
Link File
Selects the file to link to.
1 to 4
1
See page 53.
Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
[~End] End Step
[`End]
[ End]
End
Selects the state of the control and
auxiliary outputs when a profile is
ended.
[`OFF] (0)
[hold] (1)
[`OFF] (0)
See page 53.
Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature
parameters are in °F through Modbus.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.