Wa t l o w S e r i e s S D

1 4

C h a p t e r 2 I n s t a l l a n d W i r e

Figure 14a —

Output 1 Switched DC

SD_ _ - _ C _ _ - _ _ _ _

• Supply current 30 mAÎ (dc) maximum.

• Supply voltage 6 to 12VÎ (dc).

• Not recommended for switching mechanical relays.

• Output supplies power.

4

56

5
6

dc+
dc-

Internal Circuitry

dc-

dc+

6 to 12V

Î (dc)

Load

Switched DC

-

+

5

6

Figure 14b —

Output 1 Process

SD_ _ - _ F _ _ - _ _ _ _

• Analog output is scalable between 0 to 10VÎ (dc) or 0 to 20 mAÎ (dc).

• Load capability: voltage 1 kΩ minimum; current 800 Ω maximum.

• Output supplies power.

• Cannot use voltage and current output at the same time.

4

8

5
6
7

volts+ 6

com- 7

amps+ 5

Figure 14c —

Output 2 Mechanical Relay

SD_ _ - _ _ J _ - _ _ _ _

• Form A contact

• 2 A, resistive

• 125 VA pilot duty, 120/240VÅ (ac), inductive

• See Quencharc note.

• 240VÅ (ac) maximum.

• 30VÎ (dc) maximum.

• For use with ac or dc.

• Minimum load current 10 mA

• Output does not supply power.

2
3

4

3

4

normally open

common

Internal Circuitry

COM.

N.O.

Mechanical Relay

3

4

ç

Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may
result in damage to equipment
and property, and/or injury or
loss of life.

Quencharc Note:
Switching pilot duty inductive
loads (relay coils, solenoids, etc.)
with the mechanical relay or solid-
state relay output options requires
use of an R.C. suppressor.

Watlow carries the R.C. suppres-
sor Quencharc brand name, which
is a trademark of ITW Paktron.
Watlow Part No. 0804-0147-0000.

Spring clamp wiring connector
note:
To insert the wire, push the wire
into the desired connection num-
ber, and it should automatically
lock into place. To remove the
wire, press and hold the orange
release tab with a small screw-
driver. Pull the wire out of the
connection. Solid or tinned wire
recommended.

Note: To prevent ground loops,
isolation needs to be maintained
from input to output when using
switched DC or analog process
outputs.