beautypg.com

Wiring the series sd, High voltage ac power wiring, Low voltage ac power wiring – Watlow Series SD PID Profiling Controller User Manual

Page 13

background image

Wa t l o w S e r i e s S D

1 1

C h a p t e r 2 I n s t a l l a n d W i r e

Wiring the Series SD

The model number for each output option appears with its wiring dia-

gram. Check the label on the controller and compare your model number to
those shown here and to the model number breakdown in the Appendix of
this manual.

The connectors on the back of the Series SD are different for different

model numbers. Where two different combinations of connectors may appear,
we show both in the diagrams.

All outputs, including normally open and normally closed contacts, are ref-

erenced to a de-energized state (the controller has power removed).

All wiring and fusing must conform to the National Electric Code and to

any locally applicable codes as well.

Figure 11a —

High Voltage AC Power Wiring

SD_ _ - H _ _ _ - _ _ _ _ High

• Nominal voltage: 100 to 240VÅ (ac)

1

2

L2

L1

1

2
3

Figure 11b —

Low Voltage AC Power Wiring

SD_ _ - L _ _ _ - _ _ _ _ Low

• Nominal voltage: 24‡ (ac/dc)

• Class 2 power source required for agency compliance

1

2

+

-

1

2
3

Isolation Blocks

There are no electrical connections between these blocks.

Relay outputs (mechanical and solid-state) provide isolation through their
relay contacts. Each relay output is isolated from the blocks above and is
isolated from other relay outputs.

Sensor Input

Switched DC Outputs

Analog Process Outputs

Power Supply Input

EIA/TIA-485 Commu-
nications Input

Ó

Warning:
Use National Electric (NEC)
or other country-specific
standard wiring and safety
practices when wiring and
connecting this controller to
a power source and to elec-
trical sensors or peripheral
devices. Failure to do so may
result in damage to equip-
ment and property, and/or
injury or loss of life.

Note: To prevent ground loops,
isolation needs to be main-
tained from input to output
when using switched DC or
analog process outputs.

Ó

WARNING: If high voltage is
applied to a low-voltage con-
troller, irreversible damage
will occur.