beautypg.com

Programming page overview, Factory page overview – Watlow Series SD PID Profiling Controller User Manual

Page 26

background image

Wa t l o w S e r i e s S D

2 4

C h a p t e r 3 K e y s a n d D i s p l a y s

Programming Page Overview

[Prog]
[PAgE]

The Programming Page determines what parameters
the user wants to appear on the Operations Page. Se-
lect a parameter for any of the 20 (23 for the profiling
version***) Programming Page locations, P1 to P20
(P23***). These now appear on the Operations Page.
All 20 (23***) locations have parameters selected as
defaults.

To go to the Programming Page, hold down the Infinity
key ˆ, then press the Advance Key ‰, and hold both
down for about six seconds.

• Press

the

Advance

Key

‰ to move through the

parameter prompts.

• Press

the

Up

¿ or Down ¯ keys to change the pa-

rameter value.

• Press the Infinity Key ˆ at any time to return to

the Home Page.

Note: The hardware configuration and programming selections
will also determine what parameters appear on the Operations
Page. A Programming Page selection will not appear on the
Operations Page if the parameter is not active.

Note: The Programming Page is not accessible while a profile
is running. ***

Programming Page

[~~P1] Parameter Location 1 (48)
[~~P2] Parameter Location 2 (49)
[~~P3] Parameter Location 3 (50)
[~~P4] Parameter Location 4 (51)
[~~P5] Parameter Location 5 (52)
[~~P6 Parameter Location 6 (53)
[~~P7] Parameter Location 7 (54)
[~~P8] Parameter Location 8 (55)
[~~P9] Parameter Location 9 (56)
[~P10] Parameter Location 10 (57)
[~P11] Parameter Location 11 (58)
[~P12] Parameter Location 12 (59)
[~P13] Parameter Location 13 (60)
[~P14] Parameter Location 14 (61)
[~P15] Parameter Location 15 (62)
[~P16] Parameter Location 16 (63)
[~P17] Parameter Location 17 (64)
[~P18] Parameter Location 18 (65)
[~P19] Parameter Location 19 (66)
[~P20] Parameter Location 20 (67)
[~P21] Parameter Location 21 (68)***
[~P22] Parameter Location 22 (69) ***
[~P23] Parameter Location 23 (47)***

*** Profiling version only

Factory Page Overview

[FAct]
[page]

The Factory Page contains information on diagnostics,
calibration and restore-parameter functions.

To go to the Factory Page, press both the Up ¿ and
Down ¯ keys for about six seconds from the Home
Page.

• Press

the

Advance

Key

‰ to move through the

parameter prompts.

• Press

the

Up

¿ or Down ¯ keys to change the pa-

rameter value of Read/Write (R/W) parameters.

• Press the Infinity Key ˆ at any time to return to

the Home Page.

Note: Hardware configuration and programming selections de-
termine what parameters appear on the Factory Page.

Note: The Factory Page is not accessible while a profile is run-
ning. ***

Factory Page

[AMb] Ambient Temperature
[A;mn] Minimum Recorded Ambient Temperature
[A;ma] Maximum Recorded Ambient Temperature
[DSPL] Display Intensity
[A;Ot1] Output 1 Process Value
[A;Ot3] Output 3 Process Value
[rESt] Restore Factory Calibration
[Usr;r] Restore User Settings
[USr;S] Save User Settings
[PrF;r] Restore Profile Settings***
[Prf;S] Save Profile Settings***
[dFLt] Default Parameters
[O;ty1] Output 1 Type
[O;ty2] Output 2 Type
[O;ty3] Output 3 Type
[`S;Id] Software ID
[S;UEr] Software Version
[S;bld] Software Build Number
[PWr] Power Type
[`Sn-] Serial Number 1 (first four digits)
[`Sn_] Serial Number 2 (last four digits)
[tc;50] Thermocouple, 50mV
[tc;00] Thermocouple, 0mV
[tc;32] Thermocouple, 32°F
[`r;15] RTD, 15 ohm
[r;380] RTD, 380 ohm
[``U;1] Input Calibrate, 1.0 Volt
[``U;9] Input Calibrate, 9.0 Volt
[``A;4] Input Calibrate, 4.0 mA
[`A;16] Input Calibrate, 16.0 mA
[O1;1u] Output 1 Calibrate, 1.0 Volt
[O1;9u] Output 1 Calibrate, 9.0 Volt
[O1;4A] Output 1 Calibrate, 4.0 mA
[O1;16] Output 1 Calibrate, 16.0 mA
[03;1u] Output 3 Calibrate, 1.0 Volt
[03;9u] Output 3 Calibrate, 9.0 Volt
[03;4A] Output 3 Calibrate, 4.0 mA
[03;16] Output 3 Calibrate, 16.0 mA

Calibration information for the Series SD controllers is available
in pdf format. Go to www.watlow.com / Literature / Product User
Manuals and search on Series SD Calibration Manual.

This manual is related to the following products: