Chapter 10: profiling page, The profiling menu – Watlow Series SD PID Profiling Controller User Manual
Page 49
Wa t l o w S e r i e s S D
•
4 7
•
C h a p t e r 1 0 P r o f i l i n g
The Profiling Page allows you to enter your ramp and soak profile information. To go to the Profiling Page from the
Home Page, press the Advance Key ‰ and [Prof] appears in the lower display. Press the Up Key ¿ to change the
upper display to
[~yes].
• Press the Advance Key ‰ to move through the profile parameter prompts.
• Press the Up ¿ or Down ¯ keys to change the profile parameter values.
• Press the Infinity Key ˆ at any time to return to the Home Page.
Note: The Profiling Page only appears if the profiling version has been ordered (SD_R- _ _ _ _- _ _ _ _ ).
Note: The Profiling Page is only accessible if the profile is on hold or not running.
[File] File
[step} Step
[Styp} Step Type
[Stpt] Set Point Step
[soaH] Soak
Step
[``JL] Jump Loop Step {Lfil] Link
File
Step
[`EnD] End Step (End)
[tg;SP] Target Set Point
[hour] Hour
[``JF] Jump
File
{~~LF] Link
File
[`EnD] Select End Type
[hour] Hour*
[min] Minutes
[``JS] Jump
Step
[min] Minutes*
[`seC] Seconds
[``JC] Jump
Count
[`seC] Seconds*
[ent_] Event Outputs 1-3
[rate] Rate**
[wF;P} Wait-for Process Enablev
[ent_] Event Outputs 1-3 [wPr} Wait-for Process Value
[Prof] = [~Yes]
* Hour, minutes and seconds appear if Profile Type
[PtYP]
is set to
[~~ti]
.
** Rate appears if Profile Type
[PtYP]
is set to
[rAtE]
.
The Profiling Menu
Display
Parameter name
Description
Set-
tings
Range
(Integer values for Mod-
bus in parentheses.)
Default
Modbus*
(less 40,001
offset)
Read/Write
Appears if:
[FiLe]
[FiLE]
File
Represents the profile to be edited
or viewed.
[```1] (1)
[```2] (2)
[```3] (3)
[```4] (4)
1
See page 53.
Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
[StEP]
[StEP]
Step
Represents the current step of the
profile to be edited or viewed. Up to
ten steps per file.
[```1] (1)
•
• thru
•
[``10] (10)
1
See page 53.
Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
[StYp]
[StYP]
Step Type
Select from five different step types.
[`end] End (0)
[stpt] Set Point (1)
[soaH] Soak (2)
[``jl] Jump Loop (3)
[LFil] Link File (4)
[`end] (0)
See page 53.
Profiling version only.
(SD_ R - _ _ _ _ - _
_ _ _ )
Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature
parameters are in °F through Modbus.
* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.
Chapter 10: Profiling Page