Wa t l o w S e r i e s S D

3 8

C h a p t e r 6 O p e r a t i o n s

Display

Parameter name

Description

Settings

Range

Default

Modbus*

(less 40,001 offset)

Read/Write

Appears if"

[dE;CL]
[dE.CL]

Derivative Cool
Set the PID derivative time in
minutes for the cool outputs.

0.00 to 9.99 minutes (0000

to 99990)

0.00: disabled

0.00

*230, 231 R/W

At least one output is
set to

[CooL], [CL;m]

is set to

[`PId],

and

[Unit] is set to

[``SI].

[dB;CL]
[db.CL]

Dead Band Cool

An offset of the cooling pro-
portional band from the set
point.

0 to 999

(0000 to 999000)

0

*281, 282 R/W

At least one output
is set to

[Cool]

and

[CL;m] is set to

[`PId].

[C;hyS]
[C.hyS]

Cool Hysteresis

Set the control switching hys-
teresis for on/off control. This
determines how far into the
“on” region the input needs to
move before the output actu-
ally turns on.

1 to 999°F if

[`Sen] is

set to

[``tc] or [`rtd]

(1000 to 999000)

0.000 to 999.9 if

[`Sen] is

set to

[`ma] or [uolt]

(0000 to 999000)

1
1.000

*236, 237 R/W
*238, 239 R/W

At least one output
is set to

[CooL]

and

[CL;m] is set to

[on;oF].

[ProP]
[ProP]

Proportional Term

View the active proportional
term for PID diagnostics.

0.000 to 1.000****

(0000 to 1000)

NA

258 R

Any output is set to
[heat] or [Cool].

[``it]
[ it]

Integral Term

View the active integral term
for PID diagnostics.

0.000 to 1.000****

(0000 to 1000)

NA

259 R

Any output is set to
[heat] or [Cool].

[``dE]
[ dE]

Derivative Term

View the active derivative
term for PID diagnostics.

0.000 to 1.000****

(0000 to 1000)

NA

260 R

Any output is set to
[heat] or [Cool].

[ent1]
[Ent1]

Event Output 1***

Set Event Output 1 to an on
or off state.

[~off] (0) Output is off
[~~on] (1) Output is on

[~off]
(0)

351 R/W

Profiling version only.
(SD_ R - _ _ _ _ - _ _ _
_ ) Output 1 is set to
[Ent1].

[ent2]
[Ent2]

Event Output 2***

Set Event Output 2 to an on
or off state.

[~off] (0) Output is off
[~~on] (1) Output is on

[~off]
(0)

352 R/W

Profiling version only.
(SD_ R - _ _ _ _ - _ _ _
_ ) Output 2 is set to
[Ent2].

[ent3]
[Ent3]

Event Output 3***

Set Event Output 3 to an on
or off state.

[~off] (0) Output is off
[~~on] (1) Output is on

[~off]
(0)

353 R/W

Profiling version only.
(SD_ R - _ _ _ _ - _ _ _
_ ) Output 3 is set to
[Ent3].

[A1;hi]
[A1.hi]

Alarm 1 High

Set the high alarm set point.

Deviation: 0 to 9999 (0000

to 9999000)

Process: range of sensor, if

[`SEN] is set to [``tc]
or

[`rtd]

-1999 to 9999 if

[`SEN] is

set to

[`Ma] or [uolt].

(-1999000 to 9999000)

999 (dev)
1500 (pro)

*100, 101 R/W

(dev)

*104, 105 R/W

(pro)

[Ot`1] is set to
[dE;AL] or [Pr;AL].

Note: Parameters appear in the Operations Page only if activated from the programming page. See page 22 for Operations Page defaults.

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature param-
eters through Modbus are in °F, by default.

* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer. Decimal
precision is implied at three decimal places unless otherwise noted.

** Static set point version only (SD_C-_ _ _ _- _ _ _ _ ).

*** Profiling version only (SD_R-_ _ _ _- _ _ _ _ ).

**** This value multiplied by 100 equals the percent power.