Wa t l o w S e r i e s S D

4 0

C h a p t e r 7 O p e r a t i o n s f o r T R U - T U N E + ™

7

These parameters can be selected to appear in the Operations Page. Select the parameters you want to appear in
the Operations Page in the Programming Page. Press the Advance Key ‰ to enter the Operations Page and to step
through the parameters. For profiling controllers, set

[Prog] to [``no] to access the Operations Page. Press the

Infinity Key ˆ to return to the Home Page at any time.

Note: This chapter only applies to the TRU-TUNE+™ version of the Series SD (SD_E - _ _ _ _ - _ _ _ _).

Chapter 7:
Operations Parameters Table
for TRU-TUNE+™

Display

Parameter name

Description

Settings

Range

Default

Modbus*

(less 40,001 offset)

Read/Write

Appears if"

[Po;ht]
[Po.ht]

Power Heat

Displays the current heat con-
trol power.

0.0 to 100.0% power (000

to 10000) (Two decimal
places implied for Mod-
bus.)

NA

256 R

[A-M] is set to
[auto] and at least
one output is set to
[hEAt].

[Po;CL]
[Po.CL]

Power Cool

Displays the current cool con-
trol power.

0.0 to 100.0% power (000

to 10000) (Two decimal
places implied for Mod-
bus.)

NA

257 R

[A-M] is set to
[auto] and at least
one output is set to
[Cool].

[A-M]
[A-M]

Auto-Manual Mode

Set the control mode.

[auto] (0)
[Man] (1)

[auto]
(0)

25 R/W

Always appears.

[`Aut]
[ Aut]

Autotune

Start an autotune.

[`OFF] off (0)
[``On] on (1)

[`OFF]
(0)

215 R/W

At least one output
is set to

[hEAt] or

[Cool].

[t;tun]
[t.tun]

TRU-TUNE+™ Enable

Enable or disable the TRU
TUNE+ adaptive tuning
feature.

[``no] No (0)
[`yES] Yes (1)

[`yES]

350

rw

TRU-TUNE+ version
only. (SD_ E - _ _ _ _
- _ _ _ _ ).

[`CAL]
[ CAL]

Calibration Offset

Offset the input reading.

-999 to 999

(-999000 to 999000)

0.0

*85, 86 R/W

Always appears.

[ht;m]
[ht.M]

Heat Control

Method Set the heat control
method.

[`OFF] off (0)
[`PID] PID (1)
[on;of] on-off (2)

[`PID]
(1)

213 R/W

At least one output is
set to

[hEAt].

[Pb;ht]
[Pb.ht]

Proportional Band Heat

Set the proportional band for
the heat outputs.

1 to 999°F, if

[`Sen] is

set to

[``tc] or [`rtd]

(1000 to 999000)

0.000 to 999 units, if

[`Sen] is set to [`mA]
or

[uolt]. (0000 to

999000)

25 25

*335, 336 R/W
*339, 340 R/W

At least one output
is set to

[hEAt]

and

[ht;m] is set to

[`PId].

[It;hc]
[It.hc]

Integral

Set the PID integral in
seconds per repeat for all
outputs.

0.00 to 3,600 seconds per

repeat (0000 to 3600)

0.00: disabled

180.0

*343, 344 R/W

TRU-TUNE+ ver-
sion only. (SD_E - _ _
_ _ - _ _ _ _ ).

[ht;m]

and/or

[CL;m] is set

to

[`PId].

Note: Parameters appear in the Operations Page only if activated from the programming page. See page 22 for Operations Page defaults.

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature param-
eters through Modbus are in °F, by default.

* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer. Decimal
precision is implied at three decimal places unless otherwise noted.

**** This value multiplied by 100 equals the percent power.