Watlow Series SD PID Profiling Controller User Manual

Page 30

background image

Wa t l o w S e r i e s S D

2 8

C h a p t e r 5 S e t u p

Display

Parameter Name

Description

Settings

Range

(Integer values for Modbus in

parenthesis.)

Default

Modbus*

(less 40,001

offset)

Read/Write

Appears if:

[SP;Lo]
[SP.Lo]

Set Point Low Limit

Set the low range for the set
point.

Min. operating range

(of sensor) to

[SP;Hi] -

0.100: if

{`sen} is set to

{``tc}

-328 to

[SP;hi] -0.100: if

{`sen] is set to {`rtd}

-1999 to

[SP;hi] -0.001: if

{`sen} is set to [`MA],
[uolt] or [`Mu]. (Set
precision with

[P;dEC],

Process Decimal Places.)

Min. op-

erating
range
(J type):
{``tc}

-328:

{`rtd}

-999:

[`MA},
[uolt]
and
[`Mu].

*240, 241

R/W
(thermo-
couple)

*244, 245

R/W
(RTD)

*248, 249

R/W
(mA, V
or mV)

Always active.

[SP;hi]
[SP.hi]

Set Point High Limit

Set the high range for the set
point.

[rg;Lo] to max. operat-

ing range (of sensor): if
{`sen} is set to {``tc}

[SP;Lo] +0.100 to 1472: if

{`sen} is set to {`rtd}

[SP;Lo] +0.001 to 9999: if

{`sen} is set to [`MA],
[uolt] or [`Mu]. (Set
precision with

[P;dEC],

Process Decimal Places)

Max. op-

erating
range
(J type):
{``tc}

1472:

{`rtd]

999:

[`MA],
[uolt]
and
[`Mu].

*242, 243

R/W
(thermo-
couple)

*246, 247

R/W
(RTD)

*250, 251

R/W
(mA, V
or mV)

Always active.

[Ftr;E]
[Ftr.E]

Input Filter

Select filtering action.

[`OFF] (0) (no filtering)
[DiSP] (1) (filter only the

display value)

[CntL] (2) (filter the con-

trol input values)

[both] (3)

[`OFF] ( 0)

89 R/W

Always active.

[FLtr]
[FLtr]

Filter Value

Set the input filter value.

0.0 to 60.0 seconds (0000

to 60000)

0.0

*87, 88

R/W

[Ftr;E] is not set to
[`OFF].

[Ot`1]
[Ot 1]

Output 1 Function

Set Output 1 function.

[`OFF] Off (0)
[Pr;AL] Process Alarm (1)
[dE;;AL] Deviation Alarm (2)
[hEAt] Heat Control (3)
[CooL] Cool Control (4)
[E;out] Event (5) ***
[rmt] Retransmit (6)

[hEAt] (3)

143 R/W

Always
active.

Active only if Output 1
is a process output (SD_
_ - _ F _ _ - _ _ _ _)

[Ctr1]
[Ctr1]

Control Method 1

Set output 1 control type. This
parameter is only used with PID
control, but can be set anytime.

[`Ftb] Fixed Time Base

(0)

[Urtb] Variable Time

Base (1)

[`Ftb] (0)

144 R/W

[Ot`1] is set to [hEAt]
or

[CooL] and output

type is SD_ _-_ C _ _-_
_ _ _ or SD_ _-_ K _ _-_
_ _ _.

[Ftb1]
[Ftb1]

Fixed Time Base 1 (Cycle
Time)

Set the time base for Fixed Time
Base Control.

1.0 to 60.0 seconds if Out-

put 1 is a mechanical
relay (1000 to 60000)

0.1 to 60.0 seconds if Out-

put 1 is not a mechani-
cal relay (100 to 60000)

20.0: mech.

relay

5.0: solid-

state
relay

1.0:

switched
dc

*145, 146

R/W

[Ot`1] is set to [hEAt]
or

[CooL], [Ctr1] is set

to

[`Ftb] and Output 1

is not a process output.
(not SD_ _ - _ F _ _ - _
_ _ _ )

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature pa-
rameters through Modbus are in °F, by default. Writing to register 18 will toggle between °F and °C.

* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.

** Static set point version only (SD_C-_ _ _ _- _ _ _ _ ).

*** Profiling version only (SD_R-_ _ _ _- _ _ _ _ ).