Chapter 8: programming page – Watlow Series SD PID Profiling Controller User Manual
Page 45
Wa t l o w S e r i e s S D
•
4 3
•
C h a p t e r
8
P r o g r a m m i n g
Chapter 8: Programming Page
8
The Programming Page allows you to select what parameters appear on the Operations Page. To go to the Pro-
gramming Page, press both the Advance ‰ and Infinity ˆ keys for six seconds from the Home Page. [Prog] will
appear in the upper display and
[PAgE] will appear in the lower display.
• Press the Advance Key ‰ to move through the parameter prompts.
• Press the Up ¿ or Down ¯ key to change the parameter value.
• Press the Infinity Key ˆ at any time to return to the Home Page display.
Note: This chapter only applies to the static set point and profiling versions of the Series SD (SD_C or R - _ _ _ _ - _ _ _ _).
Display
Parameter name
Description
Settings
Range
(Integer values for Modbus
in parentheses.)
Default
Modbus*
(less 40,001
offset)
Read/Write
Appears if"
[``P1]
Parameter Location 1
[none]
(0) None
[`CAL]
(1) Calibration Offset
[`C-F]
(2) Temperature Units (Setup
Page)
[A1;Lo]
(3) Alarm 1 Low
[A1;hi;]
(4) Alarm 1 High
[A2;Lo]
(5) Alarm 2 Low
[A2;hi]
(6) Alarm 2 High
[A3;Lo]
(7) Alarm 3 Low
[A3;hi]
(8) Alarm 3 High
[hys1]
(9) Alarm Hysteresis 1 (Setup
Page)
[hys2]
(10) Alarm Hysteresis 2 (Setup
Page)
[hyS3]
(11) Alarm Hysteresis 3 (Setup
Page)
[addr]
(12) Modbus Device Address
(Setup Page)
[`Aut]
(13) Autotune
[A-m]
(14) Auto-Manual
[Po;ht]
(15) Power Heat
[Po;CL]
(16) Power Cool
[ht;M]
(17) Heat Control Method
[Pb;ht]
(18) Prop. Band Heat
[It;ht]
(19) Integral Heat or
[re;ht]
(19) Reset Heat
[dEht]
(20) Derivative Heat or
[ra;ht]
(20) Rate Heat
[db;ht]
(21) Dead Band Heat
[h;hys]
(22) Heat Hysteresis
[CL;M]
(23) Cool Control Method
[Pb;Cl]
(24) Prop. Band Cool
[It;Cl]
(25) Integral Cool or
[rE;Cl]
(25) Reset Cool
[dE;Cl]
(26) Derivative Cool or
[ra;Cl]
(26) Rate Cool
[db;Cl]
(27) Dead Band Cool
[C;hys]
(28) Cool Hysteresis
[prop]
(29) Proportional Term
[``It]
(30) Integral Term
[``dE]
(31) Derivative Term
[rP;rt]
(32) Ramp Rate (Setup Page)**
[Po;ht] (15) 48 R/W
All parameter loca-
tions always appear
on the Programming
Page.
Static set point ver-
sion
(SD_C - _ _ _ _ - _ _
_ _ ) P1 to P20
Profiling version
only.
(SD_R - _ _ _ _ - _ _
_ _ ) P1 to P23
[~~P2]
Parameter Location 2
[`gsd] (35) 49 R/W
[~~P3]
Parameter Location 3
[`Aut] (13) 50 R/W
[~~P4]
Parameter Location 4
[`CAL] (1)
51 R/W
[~~P5]
Parameter Location 5
[ht;m] (17) 52 R/W
[~~P6]
Parameter Location 6
[pb;ht] (18) 53 R/W
[~~P7]
Parameter Location 7
[re;ht] (19) 54 R/W
[``P8]
Parameter Location 8
[ra;ht] (20) 55 R/W
[``P9]
Parameter Location 9
[h;hys] (22) 56 R/W
[`P10]
Parameter Location 10
[CL;m] (23) 57 R/W
[`P11]
Parameter Location 11
[pb;Cl] (24) 58 R/W
[`P12]
Parameter Location 12
[re;CL] (25) 59 R/W
[`P13]
Parameter Location 13
[ra;Cl] (26) 60 R/W
[`P14]
Parameter Location 14
[C;hys] (28) 61 R/W
[`P15]
Parameter Location 15
[A1;hi] (4)
62 R/W
[`P16]
Parameter Location 16
[A1;Lo] (3)
63 R/W
[`P17]
Parameter Location 17
[A2;hi] (6)
64 R/W
[`P18]
Parameter Location 18
[A2;Lo] (5)
65 R/W
[`P19]
Parameter Location 19
[A3;hi] (8)
66 R/W
[`P20]
Parameter Location 20
[A3Lo] (7)
67 R/W
[`P21]
Parameter Location
21***
[Ent1] (32) 68 R/W
[`P22]
Parameter Location
22***
[Ent2] (33) 69 R/W
[`P23]
Parameter Location
23***
[Ent3] (34) 47 R/W
Note: All parameter locations have the same range of possible values.
**Static set point version (SD_ C - _ _ _ _ - _ _ _ _ )
***Profiling version only. (SD_ R - _ _ _ _ - _ _ _ _ )