Wa t l o w S e r i e s S D

5 6

C h a p t e r 1 0 P r o f i l i n g

Series SD Profiling Modbus Registers

This section contains information for creating, editing and running profiles using Modbus. Some of these are available
only through Modbus and others can be accessed through the front panel and Modbus. If a parameter is accessible
only through Modbus, N/A appears in the display column. Parameters appear in profiling version only.

Display

Parameter Name

Description

Settings

Range

(Integer values for Modbus

in parentheses.)

Default

Modbus*

(less 40,001

offset)

Read/Write

Appears if:

[Ptyp]
[Ptyp]

Profile Type

Set the profile ramp to time based or
rate based.

{~~ti] Time based ramp

(0)

{rate] Rate based ramp

(1)

[~~ti]
(0)

354 R/W

Always

[PStr]
[PStr]

Profile Start

Select where the profile begins the start-
ing set point of the profile, current static
set point or current process temperature.

[`Set] Static Set Point (0)
[~Pro] Process (1)

[`Set]
(0)

355 R/W

Always

[gS;dE]
[gS.dE]

Guaranteed Soak Deviation Enable

Enables the guaranteed soak deviation
function in profiles.

[`~no] Disabled (0)
[~YES] Enabled (1)

[~~no]
(0)

356 R/W

Always

[`GSd]
[ gSd]

Guaranteed Soak Deviation Value

Set the value of deviation allowed by the
guaranteed soak deviation function.

1 to 999 (1 to 999000)

1

*357, 358
R/W

[GS;dE] set to
[~YES]

N/A

Profile State

Indicates current profile status.

Profile off (0)

Profile is holding (1)

Profile is running (2)

Pre-run check failed when

starting the profile (3)

Pre-run check failed when

resuming the profle (4)

0

359 R

Available through
Modbus only.

N/A

Jump Count Step Enabled

Indicates whether a Jump Step is cur-
rently being executed.

Profile is not running or

profile is running and is
not currently executing a
Jump Step (0)

Profile is running and the

profile is currently ex-
ecuting a Jump Step (1)

0

363 R

Available through
Modbus only.

[FiLe]
[FiLE]

Start File Number

Selects the file to start running.

1 to 4

1

361 R/W

Always

[StEP]
[StEP]

Start Step Number

Selects the profile step to be run.

1 to 10

1

362 R/W

Always

[SELC]
[SELC]

Profile Select

Selects what to do when a profile is on
hold.

[`Off] Terminate current

profile (0)

[RESU] Resume running

current profile (1)

[hold] Hold current pro-

file (2)

360 R/W

If profile is holding
or running.

[`gSd]
[ GSd]

Guaranteed Soak Deviation Message

Monitors guaranteed soak deviation
status.

Message Disabled [GSD is

disabled or within range
if enabled. No message is
flashing] (0)

Message Enabled [GSD

outside range and a mes-
sage is flashing] (1)

0

364 R

[GS;dE] set to
[~YES]

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature pa-
rameters are in °F through Modbus.

* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.