Watlow Series SD PID Profiling Controller User Manual

Page 29

background image

Wa t l o w S e r i e s S D

2 7

C h a p t e r 5 S e t u p

Display

Parameter Name

Description

Settings

Range

(Integer values for Modbus in

parenthesis.)

Default

Modbus*

(less 40,001

offset)

Read/Write

Appears if:

[Sc;Lo]
[Sc.Lo]

Process Scale Low

Set the low scale for process
inputs.

0.00 to 20.00 mA: if

[`Sen] is set to [`mA]
(0000 to 20000)

0.00 to 10.00 V: if

[`Sen]

is set to

[uoLt] (0000 to

10000)

0.00 to 50.00 mV: if

[`Sen] is set to [~mu]
(0000 to 50000)

4.00 mA

0.00 V

0.00 mV

*73, 74 R/

W (mA)

*77, 78 R/

W (V)

*331, 332

R/W
(mV)

[`Sen] is set to [`mA],

[`Sen] is set to [uolt].

[`Sen] is set to [`mu].

[Sc;hi]
[Sc.hi]

Process Scale High

Set the high scale for process
inputs.

0.00 to 20.00 mA: if

[`Sen] is set to [`mA]
(0000 to 20000)

0.00 to 10.00V: if

[`Sen]

is set to

[uoLt] (0000 to

10000)

0.00 to 50.00 mV: if

[`Sen] is set to [~mu]
(0000 to 50000)

20.00 mA

5.00 V

50.00 mV

*75, 76 R/

W (mA)

*79, 80 R/

W (V)

*333, 334

R/W
(mV)

[`Sen] is set to [`mA],

[`Sen] is set to [uolt].

[`Sen] is set to [`mu],

[P1;LE]
[P1.LE]

Process Input Low Error

Set the low process value that
will cause an error to occur for
the process input.

-1.00 to 10.00 mA (-100

to 1000)

-1.00 to 5.00 V (-100 to

500)

-1.00 to 25.00 mV (-100 to

2500) (two decimal plac-
es implied for Modbus)

-1.00 mA

-1.00 V

-1.00 mV

325 R/W

(mA)

327 R/W

(V)

329 R/W

(mV)

[`Sen] is set to [`mA].

[`Sen] is set to [uolt].

[`Sen] is set to [`mu].

[P1;HE]
[P1.HE]

Process Input High Error

Set the high process value that
will cause an error to occur for
the process input.

10.00 to 21.00 mA (1000

to 2100)

5.00 to 11.00 V (500 to

1100)

25.00 to 51.00 mV (2500

to 5100) (two decimal
places implied for Mod-
bus)

21.00 mA

11.00 V

51.00 mV

326 R/W

(mA)

328 R/W

(V)

330 R/W

(mV)

[`Sen] is set to [`mA],
[uolt]. or [`mu].

[rg;Lo]
[rg.Lo]

Units Scale Low

Set the low range for process
input units.

-1999 to 9999 (1999000 to

9999000) (Set precision
with

[P;dEC], Process

Decimal Places.)

-1999

*81, 82

R/W

[`Sen] is set to [`mA],
[uolt]. or [`mu].

[rg;hi]
[rg.hi]

Units Scale High

Set the high range for process
input units.

-1999 to 9999 (-1999000

to 9999000) (Set preci-
sion with

[P;dEC], Pro-

cess Decimal Places.)

9999

*83, 84

R/W

[`Sen] is set to [`mA],
[uolt]. or [`mu].

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature pa-
rameters through Modbus are in °F, by default. Writing to register 18 will toggle between °F and °C.

* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.

** Static set point version only (SD_C-_ _ _ _- _ _ _ _ ).

*** Profiling version only (SD_R-_ _ _ _- _ _ _ _ ).