C h a p t e r 5 S e t u p

Display

Parameter Name

Description

Settings

Range

(Integer values for Modbus in

parenthesis.)

Default

Modbus*

(less 40,001

offset)

Read/Write

Appears if:

[r3;Lo]
[r3.Lo]

Output 3 Retransmit Low
Scale

Set the low scale for the retrans-
mit output.

-1999.0 to 9999.0

(-1999000 to 9999000)

0 *316,

317

R/W

Output 3 is a process
output (SD_ _ - _ _ _ F
- _ _ _ _ ) and

[Ot`3] is

set to

[rmt].

[r3;hi]
[r3.hi]

Output 3 Retransmit High
Scale

Set the high scale for the re-
transmit output.

-1999.0 to 9999.0

(-1999000 to 9999000)

500

*318, 319

R/W

Output 3 is a process
output (SD_ _ - _ _ _ F
- _ _ _ _ ) and

[Ot`3] is

set to

[rmt].

[r3;CO]
[r3.CO]

Output 3 Retransmit Offset

Set the offset value for the re-
transmit output.

-999.0 to 999.0

(-999000 to 999000)

0

*320, 321

R/W

Output 3 is a process
output (SD_ _ - _ _ _ F
- _ _ _ _ ) and

[Ot`3] is

set to

[rmt].

[hyS1]
[hyS1]

Alarm 1 Hysteresis

Set the hysteresis for an alarm.
This de- termines how far into
the safe region the input needs
to move before the alarm can be
cleared.

0.0 to 999.0

(0000 to 999000)

1.0

*106, 107

R/W

[Ot`1] is set to [dE;AL]
or

[Pr;AL].

[Lgc1]
[Lgc1]

Alarm 1 Logic

Select the alarm output condi-
tion in the alarm state.

[AL`C] closed on alarm

(0)

[AL`O] open on alarm (1)

[AL`C] (0)

164 R/W

[Ot`1] is set to [dE;AL]
or

[Pr;AL].

[LAt1]
[LAt1]

Alarm 1 Latching

Turn J on or off.

[nLAt] off (0)
[`LAt] on (1)

[nLAt] (0)

108 R/W

[Ot`1] is set to [dE;AL]
or

[Pr;AL].

[SiL1]
[SiL1]

Alarm 1 Silencing

Turn alarm silencing on or off.

[`OFF] off (0) no silencing
[``On] on (1) silencing

[`OFF] (0)

109 R/W

[Ot`1] is set to [dE;AL]
or

[Pr;AL].

[dSP1]
[dSP1]

Alarm 1 Message

Displays an alarm message
when an alarm is active.

[`OFF] off (0) no message
[``On] on (1) message

[``On] (1)

110 R/W

[Ot`1] is set to [dE;AL]
or

[Pr;AL].

[hyS2]
[hyS2]

Alarm 2 Hysteresis

Set the hysteresis for an alarm.
This determines how far into
the safe region the input needs
to move before the alarm can be
cleared.

0.0 to 999.0 (0000 to

999000)

1.0

*121, 122

R/W

[Ot`2] is set to [dE;AL]
or

[Pr;AL].

[Lgc2]
[Lgc2]

Alarm 2 Logic

Select the alarm output condi-
tion in the alarm state.

[AL`C] closed on alarm

(0)

[AL`O] open on alarm (1)

[AL`C] (0)

175 R/W

[Ot`2] is set to [dE;AL]
or

[Pr;AL].

[LAt2]
[LAt2]

Alarm 2 Latching

Turn alarm latching on or off.

[nLAt] off (0)
[`LAt] on (1)

[nLAt] (0)

123 R/W

[Ot`2] is set to [dE;AL]
or

[Pr;AL].

[SiL2]
[SiL2]

Alarm 2 Silencing

Turn alarm silencing on or off.

[`OFF] off (0) no silencing
[``On] on (1) silencing

[`OFF] (0)

124 R/W

[Ot`2] is set to [dE;AL]
or

[Pr;AL].

[dSP2]
[dSP2]

Alarm 2 Message

Displays an alarm message
when an alarm is active.

[`OFF] off (0) no message
[``On] on (1)

[``On] (1)

125 R/W

[Ot`2] is set to [dE;AL]
or

[Pr;AL].

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with Modbus. All temperature pa-
rameters through Modbus are in °F, by default. Writing to register 18 will toggle between °F and °C.

* Low register numbers contain the two higher bytes; high register numbers contain the two lower bytes of the four-byte integer.
Decimal precision is implied at three decimal places unless otherwise noted.

** Static set point version only (SD_C-_ _ _ _- _ _ _ _ ).

*** Profiling version only (SD_R-_ _ _ _- _ _ _ _ ).