Chapter 7 RMA Communications

Profibus DP RMA LED Indicators

Viewing the unit from the front and then looking on

top of the RMA two bicolor LED's can be seen where

only the front one is used. Definition follows:
Closest to the Front

Indicator LED

Description

Red

Profibus network not detected

Red

Flashing

Indicates that the Profibus card is

waiting for data exchange.

Green

Data exchange mode

To learn more about Profibus point your browser to

http://www.profibus.org

.

Saving Settings to Non-volatile Memory

Any changes made from the RUI are always saved to

non-volatile memory (EEPROM) of the module it is

connected to. If a module loses power or is switched

off, its settings will be restored when power is reap-

plied.

The EEPROM has a limited life calculated to

be approximately 1,000,000 writes. Over the life of

any given RM module this limitation would not be a

problem when changes are made exclusively from the

RUI. However, if an RM module is receiving instruc-

tions from a PLC or a computer through a network

connection where the frequency of the write opera-

tions could be high, the EEPROM life could expire

much quicker.

By default, settings made through the network

are not saved to nonvolatile memory (59). However,

as stated above, changes made via the RUI are saved

to EEPROM, regardless of the setting of non-volatile

memory save. This parameter can be changed via the

communications network in use, through the RUI or

via EZ-ZONE Configurator software. This parameter

can be found in the User's Guide for each RM module

in the Setup Page under the Communications Menu.

Note:

This setting must be changed to the desired setting

for each module individually.

RMA with Profibus DP Gateway

OIT, PC, PLC

Profibus DP

RMA/Gateway

[gtW]

1 = RM 1

[gtW]

4 = RM 4

Profibus Slot

Offset

0

Profibus Slot

Offset

20

Profibus Slot

Offset

40

Profibus Slot

Offset

60

Address Lock

[a;loc]

= Yes or No

[Com]

Profibus Address

[p;add]

= 0 - 126

RMA/Gateway ( [gtW] ) Setup

Gateway Prompts

[gtW]

= 1 - 17

(Gateway Instance)

[Du;En]

= Yes or No

(Enable gateway instance)

[Du;st]

= [On] or [off]

(Device Status)

[`s;of]

= 0 - 254

(Profibus Slot Offset)

Watlow Standard Bus

(Daisy chain EIA-485)

EZ-ZONE Controllers

1 - 17 maximum