Chapter 7 RMA Communications
Profibus DP RMA LED Indicators
Viewing the unit from the front and then looking on
top of the RMA two bicolor LED's can be seen where
only the front one is used. Definition follows:
Closest to the Front
Indicator LED
Description
Red
Profibus network not detected
Red
Flashing
Indicates that the Profibus card is
waiting for data exchange.
Green
Data exchange mode
To learn more about Profibus point your browser to
Saving Settings to Non-volatile Memory
Any changes made from the RUI are always saved to
non-volatile memory (EEPROM) of the module it is
connected to. If a module loses power or is switched
off, its settings will be restored when power is reap-
plied.
The EEPROM has a limited life calculated to
be approximately 1,000,000 writes. Over the life of
any given RM module this limitation would not be a
problem when changes are made exclusively from the
RUI. However, if an RM module is receiving instruc-
tions from a PLC or a computer through a network
connection where the frequency of the write opera-
tions could be high, the EEPROM life could expire
much quicker.
By default, settings made through the network
are not saved to nonvolatile memory (59). However,
as stated above, changes made via the RUI are saved
to EEPROM, regardless of the setting of non-volatile
memory save. This parameter can be changed via the
communications network in use, through the RUI or
via EZ-ZONE Configurator software. This parameter
can be found in the User's Guide for each RM module
in the Setup Page under the Communications Menu.
Note:
This setting must be changed to the desired setting
for each module individually.
RMA with Profibus DP Gateway
OIT, PC, PLC
Profibus DP
RMA/Gateway
[gtW]
1 = RM 1
[gtW]
4 = RM 4
Profibus Slot
Offset
0
Profibus Slot
Offset
20
Profibus Slot
Offset
40
Profibus Slot
Offset
60
Address Lock
[a;loc]
= Yes or No
[Com]
Profibus Address
[p;add]
= 0 - 126
RMA/Gateway ( [gtW] ) Setup
Gateway Prompts
[gtW]
= 1 - 17
(Gateway Instance)
[Du;En]
= Yes or No
(Enable gateway instance)
[Du;st]
= [On] or [off]
(Device Status)
[`s;of]
= 0 - 254
(Profibus Slot Offset)
Watlow Standard Bus
(Daisy chain EIA-485)
EZ-ZONE Controllers
1 - 17 maximum