beautypg.com

Ethernet indicator led's – Watlow EZ-ZONE RMA Modul User Manual

Page 57

background image

Watlow EZ-ZONE

®

RMA Module

54

Chapter 7 RMA Communications

Application Note:

Assume that in the following graphic there are 4 RMC

modules on the network with each having 4 instances

of an Analog Input. If it is desired to access all of the

Analog Inputs from each module the CIP offset must,

at a minimum, have an offset of 4 between each mod-

ule (gateway instance). If the offset for each module is

set as shown on the following page, the 4th instance

would not be available. As another example, looking

at the RMC User's Guide in the Setup Page under the

Variable Menu, it shows that there are 8 instances

available. If all 8 for each module are to be made

available to the Master (OIT, PC, PLC) then the off-

sets should at a minimum be set as shown below:

RM1 = 0, RM2 = 9, RM3 = 18 and RM4 = 27

Using the RMC User's Guide look at the Operations

Page and then the Analog Input Menu. There you

will find the class, instance and attribute of the first

instance of the Analog Input Value for RM 2 to be

the following:

Class = 104 or (0x68)

Instance =

5

Attribute = 1

This information would be needed to execute an ex-

plicit message to read this parameter. Notice that the

instance above is identified as 5 and not 1 as listed

in the RMC documentation. The CIP offset is always

added to the documented instance. Using the follow-

ing graphic the offset entries are listed below.

1. RUI prompt entry for gateway instance 1 (RM 1)

follows: [`oSt] = 0
RUI prompt entry for gateway instance 2 (RM 2) fol-

lows: [`oSt] = 4
RUI prompt entry for gateway instance 3 (RM 3) fol-

lows: `oSt] = 8
RUI prompt entry for gateway instance 4 (RM 4) fol-

lows: [`oSt] = 12
Likewise, to read the Analog Input Value instance 2

of RM 4 the following information would need to be

entered in the message instruction:

Class = 104 or (0x68)

Instance =

14

or (0x0E)

Attribute = 1

[ao;nb]

CIP Implicit Output (Produced) Assembly

Size, used exclusively when communicating

implicitly. For any given RMA gateway in-

stance (1 - 17), the output assembly size will

never be greater than 40, 32 bit members.

The user entry ranges from 0 to 40.

[ai;nb]

CIP Implicit Input (Consumed) Assembly

Size, used exclusively when communicating

implicitly. For any given RMA gateway in-

stance (1 - 17), the input assembly size will

never be greater than 40, 32 bit members.

The user entry ranges from 0 to 40.

Note:

When configuring the RMA assemblies for each gate-

way instance it is important to note that the maxi-

mum number of implicit input/output members using

EtherNet/IP cannot exceed 100. A network could have

up to 5 EZ-ZONE controllers with 20 members each

maximum or the 100 members can be divided any way

the user would like as long as 40 I/O members per

module are not exceeded.

Using the graphic above as an example, if:
[Gtw]

instance 1 has [ai;nb] and [ao;nb] set to 5

[Gtw]

instance 2 has [ai;nb] and [ao;nb] set to 5

[Gtw]

instance 3 has [ai;nb] and [ao;nb] set to 5

[Gtw]

instance 4 has [ai;nb] and [ao;nb] set to 5

Each of the four RM modules will contain the first

5 members of the I/O assembly and this information

would then be passed implicitly to the Master on the

EtherNet/IP network.

Note:

In the above graphic there are several prompts omit-
ted for the sake of saving some space. When the
Ethernet addressing mode is set to Fixed the user
will find several more prompts that will follow the
prompts shown for "Ethernet Addressing Mode" relat-
ed to specifying the actual IP [ip;f1] - [ip;f4], subnet
[ip;s1]

- [ip;s4] and the gateway [ip;g1] - [ip;g4]

(external gateway) addresses. If set to receive an IP
address from a host [dhCp] computer, the prompts
shown are accurate.

Note

:

When changing the RMA IP address, power must be

cycled for the new address to take affect.

Ethernet Indicator LED's

The RMA has four indicator LED's on the top of the

module for Ethernet, two of which are not used for

Modbus TCP. The Module Status and Network Sta-

tus LED’s apply only when EtherNet/IP is enabled.

The characteristics of the Activity and Link indicator

LED’s are defined in the Ethernet specification.

This is a view of the RMA module
looking down into the top where
the arrow is pointing towards the
front of the module.
Left Front (

blue

circle):

- Green accessing SD card.
- Red accessing internal memory
Left Rear (

blue

circle):

- Flashing green heartbeat
- Red boot loader activity
Right, from front to rear (

red

circle):
- Active Status - Ethernet
- Link Status - Ethernet
- MS (Module Status - CIP)
- NS (Network Status - CIP)