beautypg.com

Watlow EZ-ZONE RMA Modul User Manual

Page 22

background image

Watlow EZ-ZONE

®

RMA Module

19

Chapter 2 Install and Wire

Conventions Used in the Menu Pages

To better understand the menu pages that follow

review the naming conventions used. When encoun-

tered throughout this document, the word "default"

implies as shipped from the factory. Each page (Op-

erations, Setup and Factory) and their associated

menus have identical headers defined below:

Header Name

Definition

Display

Visually displayed infor-

mation from the control.

Parameter Name

Describes the function of

the given parameter.

Range

Defines options available

for this prompt, i.e., min/

max values (numerical),

yes/no, etc... (further ex-

planation below).

Default

Values as delivered from

the factory.

Modbus Relative Ad-

dress

Identifies unique param-

eters using either the

Modbus RTU or Modbus

TCP protocols (further ex-

planation below).

CIP (Common Indus-

trial Protocol)

If used in conjunction

with an RMA module

identifies unique param-

eters using either the De-

viceNet or EtherNet/IP

protocol (further explana-

tion below).

Profibus Index

If used in conjunction

with an RMA module

identifies unique param-

eters using Profibus DP

protocol (further explana-

tion below).

Parameter ID

Identifies unique param-

eters used with other soft-

ware such as, LabVIEW.

Data Type R/W

uint = Unsigned 16 bit

integer

dint = Signed 32-bit,

long

string = ASCII (8 bits

per character)

float = IEEE 754 32-bit
RWES = Readable

Writable

EEPROM (saved)

User Set (saved)

Display
When the RMA module is used in conjunction with

the RUI (optional equipment) visual information

from the module is displayed to the observer using

a fairly standard 7 segment display. Due to the use

of this technology, several characters displayed need

some interpretation, see the list below:

[1]

= 1

[0]

= 0

[i]

= i

[r]

= r

[2]

= 2

[a ]

= A

[j ]

= J

[s]

= S

[3]

= 3

[ h]

= b

[H]

= K

[ t]

= t

[4]

= 4

[c]

, [C] = c

[L]

= L

[U]

= u

[5]

= 5

[d ]

= d

[ m ]

= M

[u]

= v

[6]

= 6

[ e]

= E

[n]

= n

[ w ]

= W

[7]

= 7

[ f]

= F

[o]

= o

[y ]

= y

[8]

= 8

[g ]

= g

[ p]

= P

[2]

= Z

[9]

= 9

[ h]

= h

[q ]

= q

Range
Within this column notice that on occasion there will

be numbers found within parenthesis. This number

represents the enumerated value for that particular

selection. Range selections can be made simply by

writing the enumerated value of choice using any of

the available communications protocols. As an ex-

ample, turn to the Operations Page and look at the

Backup Menu. To initiate a backup using Modbus

simply right the value of 1644 (save) to Modbus reg-

ister 401271.
Communication Protocols
The RMA module comes with the standard offering

of Watlow's Standard Bus protocol used primarily

for inter-module communications as well as for con-

figuration using EZ-ZONE Configurator software

(free download from Watlow's web site (

http://www.

watlow.com

). Along with Standard Bus, the RMA

module has options for several different protocols

listed below:
- Modbus RTU 232/485
- EtherNet/IP, Modbus TCP
- DeviceNet
- Profibus DP
Modbus RTU Protocol
All Modbus registers are 16-bits and as displayed

in this manual are relative addresses (actual). Some

legacy software packages limit available Modbus

registers to 40001 to 49999 (5 digits). Many applica-

tions today require access to all available Modbus

registers which range from 400001 to 465535 (6 dig-

its). Watlow controls support 6 digit Modbus regis-

ters.

Note:

In this User's Guide, all values shown representing

Modbus addresses are added to 400,001 or 40,001 to

acquire the absolute address. As an example, notice

above (under the Range header) the Modbus address

identified for Backup. Compare this to the value list-

ed for this same parameter found in the Operations