beautypg.com

Watlow EZ-ZONE RMA Modul User Manual

Page 31

background image

Watlow EZ-ZONE

®

RMA Module

28

Chapter 4 Setup Page

Access Module

Setup Page

Display

Parameter name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Param-

eter

ID

Data

Type

& Read/

Write

[M;oF]
[M.oF]

Local Remote Gateway (1 to

17)

Modbus Address Offset

When multiple EZ-ZONE

controllers are used over

Modbus the value entered

allows for parameter dif-

ferentiation from control to

the next.

0 to 65,535

0

454

{offset 20}

0x7C

(124)

1 to 11

(17)

3

24

24003 uint

RWE

[`oSt]
[ oSt]

Local Remote Gateway (1 to

17)

CIP Instance Offset

When executing explicit

messages with multiple

EZ-ZONE controllers the

number entered allows for

differentiation from control

to control.

0 to 255

0

456

{offset 20}

0x7C

(124)

1 to 11

(17)

4

25

24004 uint

RWE

[Ao;nb]
[ Ao.nb]

Gateway (1 to 17)

CIP Implicit Assembly

Output Member Quantity

The number entered deter-

mines the size of the output

(produced) assembly.

0 to 40

- - - -

466

{offset 20}

0x7C

(124)

1 to 11

(17)

9

26

24009 uint

RWE

[Ai;nb]
[Ai.nb]

Gateway (1 to 17)

CIP Implicit Assembly In-

put Member Quantity

The number entered deter-

mines the size of the input

(consumed) assembly.

0 to 40

468

{offset 20}

0x7C

(124)

1 to 11

(17)

0x0A (10)

27

24010 uint

RWE

Note: Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EEPROM

S: User Set