Rma with devicenet gateway rma/gateway – Watlow EZ-ZONE RMA Modul User Manual

Page 59

background image

Watlow EZ-ZONE

®

RMA Module

56

Chapter 7 RMA Communications

Module Status (MOD)

Indicator LED

Description

Off

No power is applied to the de-

vice.

Flashing Green-

Red

The device is performing a

self-test.

Flashing Red

Major Recoverable Fault.

Red

Major Unrecoverable Fault.

Green

The device is operating nor-

mally.

Network Status (NET)

Indi-

cator

LED

Description

Off

The device is not online. The device has not

completed the duplicate MAC ID test yet.

The device may not be powered..

Green

The device is online and has connections in

the established state. For a Group 2 Only

device it means that the device is allocated

to a Master.

Red

Failed communication device. The device

has detected an error that has rendered

it incapable of communicating on the net-

work (duplicate MAC ID or Bus-off).

Flash-

ing

Green

The device is online, but no connection has

been allocated or an explicit connection has

timed out.

Flash-

ing

Red

A poll connection has timed out.

Setting DeviceNet Communication Parameters
from the RUI Front Panel

Valid DeviceNet node addresses range from 0 - 63

and there are three available baud rates (network

speed) for the user to choose from: 125Kb, 250Kb,

or 500Kb. The EZ-ZONE RMA factory defaults are

listed below:

Node address = 63, Baud rate = 125Kb
If the node address needs to be changed, go to the

RMA "Setup Page" following the steps below:

1. Push and hold the up and down arrow keys on

the front of the RUI for six seconds to go the

Setup Menu.

2. If not already visible push the up or down arrow

key until [CoM] (Communications Menu) ap-

pears in upper display and [`SEt] in the lower

display.

3. Push the green Advance Key

to enter the

Communications Menu where the lower display

shows [`Ad;d] and the top display shows the

current DeviceNet node address.

4. Push the up or down arrow to change the Devi-

ceNet node address.

5. Push the green Advance Key

once to change

the baud rate where the lower display shows
[baud]

and the top display shows the current

DeviceNet baud rate.

6. Push the up or down arrow to change to the de-

sired baud rate (125Kb, 250Kb, or 500Kb)

7. Push the green Advance Key

once to enable/

disable the DeviceNet quick connect feature.

The lower display shows [`fC;e] and the top

display will show [``no] or [`yes] based on

the current setting.

RMA with DeviceNet Gateway

RMA/Gateway

[gtW]

1 = RM 1

[gtW]

4 = RM 4

DeviceNet

PLC, PC, OIT

Network Baud Rate

[baud]

= [125], [250] or [500] Kb

[Com]

DeviceNet Node Address

[Ad;d]

= [0-63]

DeviceNet Quick Connect

[Fc;e]

= Yes or No

RMA/Gateway ( [gtW] ) Setup

Gateway Prompts

CIP Offset

1-3

CIP Offset

5-7

CIP Offset

9-11

CIP Offset

13-255

[oSt]

= 0 - 255

(CIP Offset)

[Ai;nb]

= 0 - 40

(CIP Consumed Assembly Size)

[Ao;nb]

= 0 - 40

(CIP Produced Assembly Size)

[gtW]

= 1 - 17

(Gateway Instance)

[Du;En]

= Yes or No

(Enable gateway instance)

[Du;st]

= [On] or [off]

(Device Status)

Watlow Standard Bus

(Daisy chain EIA-485)

EZ-ZONE Controllers

1 - 17 maximum