beautypg.com

Data logging menu, Backup menu, Data logging menu backup menu – Watlow EZ-ZONE RMA Modul User Manual

Page 25

background image

Watlow EZ-ZONE

®

RMA Module

22

Chapter 3 Operations Page

Access Module • Operations Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

& Read/

Write

[dLog]
[oPEr]
Data Logging Menu

[Stat]
[Stat]

Data Logging

Status

Status indicates the status

of the data logging function.

OK means logging can be

started or can continue. No

Memory can indicate the

memory card is full or not

present.

[no;M]

No Memory (1637)

[``oH]

OK (138)

- - - -

1452

0x89

(137)

1

2

50

37002

uint
R

[AME]
[AME]

Data Logging

Available Memory

Available Logging Memory

indicates the remaining

space available for logging

in kilobytes.

0 to 9,999

- - - -

1456

0x89

(137)

1

4

52

37004

uint
R

[`A;ti]
[ A.ti]

Data Logging

Available Logging Time

Available Logging Time

when logging is active, in-

dicates the remaining time

that logging can continue in

hours. When logging is not

active, indicates zero.

0 to 9,999 hours

- - - -

1458

0x89

(137)

1

5

53

37005

uint
R

[bCUP]
[oPEr]
Backup Menu

[Stat]
[Stat]

Backup (1 to 6)

Status

Status indicates the status

of the configuration backup

function.

Off - means no backup or re-

store action is running.
Save - indicates the con-

figuration of a zone is being

saved to backup memory.
Restore - indicates a saved

configuration is being re-

stored to a zone.
Monitor - When backup is

set to restore on a change

the RMA will check to see if

a module serial number has

changed. If so, a restore will

take place for that module.
Complete - indicates that

the restoration is complete.
Error - indicates that the

last action failed.

[`oFF]

Off (62)

[saue]

Save (1644)

[rest]

Restore (1645)

[mon]

Monitor (1187)

[Cplt]

Complete (18)

[`err]

Error (28)

Off

1274

0x8A

(138)

1 to 6

3

60

38003

uint
R

Note: Some values will be rounded off to fit in the four-character display . Full values can
be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EEPROM

S: User Set