beautypg.com

Watlow EZ-ZONE RMA Modul User Manual

Page 23

background image

Watlow EZ-ZONE

®

RMA Module

20

Chapter 2 Install and Wire

Page under the Backup Menu.

For parameters listed as float notice that only

one (low order) of the two registers is listed, this is

true throughout this document. By default, the low

order word contains the two low bytes of the 32-bit

parameter. As an example, look in the RMA Setup

Page for the Real Time Clock Value. Find the column

identified in the header as Modbus and notice that it

lists register 1424. Because this parameter is a float

it is actually represented by registers 1424 (low or-

der bytes) and 1425 (high order bytes). The Modbus

specification does not dictate which register should

be high or low order so Watlow provides the user the

ability to swap this order (Setup Page, Communica-

tions Menu) from the default low/high to high/low.
It should also be noted that some of the cells in the

Modbus column contain wording pertaining to an

offset. Several parameters in the RMA contain more

than one instance; such as, Data Log points (250),

Variables (12), Gateway Instances (16), etc... The

Modbus register shown always represents instance

one. Take for an example the logging point param-

eter found in the RMA Setup Page under the Log

Point Menu. Instance one for the Source Function

is shown as address 1470 and the offset to the next

instance is identified as +16. If there was a desire to

read or write to instance 3 simply add 32 to 1470 to

find its address, in this case, the instance 3 address

for Log Point Source Function 3 is 1502.
RMA _ - A [2, 3] _ _ - A A _ _
To learn more about the Modbus protocol point your

browser to

http://www.modbus.org

.

Common Industrial Protocol (CIP)

DeviceNet & Ethernet/IP
Both DeviceNet and EtherNet/IP use open object

based programming tools and use the same address-

ing scheme. In the following menu pages notice the

column header identified as CIP. There you will find

the Class, Instance and Attribute in hexadecimal,

(decimal in parenthesis) which makes up the address-

ing for both protocols.

Note:

The RMA module equipped with EtherNet/IP supports

implicit and unconnected explicit messages.

Data Types Used with CIP

uint

= Unsigned 16 bit integer

int

= Signed 16-bit

dint

= Signed 32-bits, long

real

= Float, IEEE 754 32-bit

string

= ASCII, 8 bits per character

sint

= Signed 8 bits , byte

RMA _ - A [3] _ _ - A A _ _
To learn more about the DeviceNet and EtherNet/IP

protocol point your browser to

http://www.odva.org

.

Profibus DP
To accommodate for Profibus DP addressing the fol-

lowing menus contain a column identified as Profibus

Index. Data types used in conjunction with Profibus

DP can be found in the table below.
Data Types Used with Profibus DP

Word

= Unsigned 16 bit

INT

= Signed 16-bit Integer

dint

= Signed 32-bit Integer

REAL

= Float, IEEE 754 32-bit

CHAR

= ASCII, 8 bits per character

BYTE

= 8 bits

RMA _ - A [6] _ _ - A A _ _
To learn more about the Profibus DP protocol point

your browser to

http://www.profibus.org