Instruction 20- Multiplexer
Expression:
Space Requirement: 1 line x 6 column Location Requirement: Middle, Right rail
Function:
When the input is ON, the data of the register which is designated by B in the table, size n
starting with A, is transferred to C.
Execution Condition:
Input
Operation
Output
OFF
No execution
OFF
ON
Normal Execution
OFF
Pointer Over (no execution)
ON
Operand:
Coil or Bit
Register
Constant
Index
Name
X Y
B
S
T.
C.
M
X
W
Y
W
B
W
S
W
T C
D
I
J
K
M
W
A
Start of
Table
√
√
√
√
√ √
√
n
Table Size
1-64
B
Pointer
√
√
√
√
√ √
√
√
√
√
0-63
C
Destination
√
√
√
√ √
√
√
√
√
√
Example:
When B010 is ON, the register data which is designated by BW30 is read from the table D0500
to D0509 (10 registers size), and stored in D0005.
If the data of BW30 is 7, D0507 data is transferred to D0005.