MAPware-7000 Ladder Logic Guide
1010-1041 rev. 00
Instruction 92- Moving Average
Expression:
Space Requirement: 1 line x 6 column Location Requirement: Middle, Right rail
Function:
When the input is ON, this instruction calculates the average value of the last (n) scanned values
in register A, and stores the average in register C. The number of scans (n) allowed is 1 to 64.
Register B is the start of the data table, (where scanned values are stored). Finally, Register C+1
is used as a pointer to the data table.
This instruction is primarily used for filtering analog input signals.
Execution Condition:
Input
Operation
Output
OFF
No execution
OFF
ON
Execution
ON
Operand:
Coil or Bit
Register
Constant
Index
Name
X
Y B
S
T.
C.
M
X
W
Y
W
B
W
S
W
T C
D
I
J
K
M
W
A
Input Data
√
√
√
√
√ √
√
√
√
√
√
n
Input Data
1-64
B
Start of
Table
√
√
√
√ √
√
C
Output Data
√
√
√
√
√ √
√
√
√
Example:
Register XW04 (A) is read during every scan of the ladder logic. Number of scans (n) is set to 5.
The start of the data table (B) is D0900. Therefore, registers D0900-D0904 are used to store the
values read from XW04. D0010 (C) is used to store the calculated average and D0011 (C+1) is
used by this instruction as a pointer: