Instruction 4- rising edge (transitional contact) – Maple Systems MAPware-7000 User Manual
Page 25
17
MAPware-7000 Ladder Logic Guide
1010-1041 rev. 00
Instruction 4- Rising Edge (Transitional Contact)
Expression:
Space Requirement: 1 line x 1 column Location Requirement: Left rail, Middle
Function:
When the input at last scan is OFF and the input at this scan is ON, the output is turned ON. This
instruction is used to detect the input changing from OFF to ON.
Execution Condition:
Input
Operation
Output
OFF
Regardless of the input state at last scan.
OFF
ON
When the input state at last scan is OFF.
ON
When the input state at last scan is ON.
OFF
Operand:
No operand is required.
Example:
Timing Diagram:
Coil Y0002 comes ON for only 1 scan when the device X0000 comes ON.