Instruction 75- on timer – Maple Systems MAPware-7000 User Manual
Page 125
117
MAPware-7000 Ladder Logic Guide
1010-1041 rev. 00
Instruction 75- ON Timer
Expression:
Space Requirement: 1 line x 5 column Location Requirement: Middle, Right rail
Function:
When the input is changed from OFF to ON, timer updating for the timer register B is started.
The elapsed time is stored in B. When the specified time by A has elapsed after the input came
ON, the output and the timer device corresponding to B are turned ON. (Timer updating is stopped)
When the input is changed from ON to OFF, B is cleared to 0, and the output and the timer
device are turned OFF. The available data range for operand A is 0 to 32767.
Execution Condition:
Input
Operation
Output
OFF
No operation (timer is not updating)
OFF
ON
Elapsed time < preset time (timer is updating)
ON
Elapsed time > preset time (timer is not updating)
OFF
Operand:
Coil or Bit
Register
Constant
Index
Name
X
Y B
S
T.
C.
M
X
W
Y
W
B
W
S
W
T C
D
I
J
K
M
W
A
Preset Time
√
√
√
√
√ √
√
√
√
√
0-32767
B
Elapsed Time
√
Example:
Y021 (and the timer device T.000) is turned ON 2 seconds after X000 came ON.
Preset Less than
time (2s) preset time
Note: