beautypg.com

Instruction 55- logic exclusive or – Maple Systems MAPware-7000 User Manual

Page 100

background image

MAPware-7000 Ladder Logic Guide

92

1010-1041 rev. 00

Instruction 55- Logic Exclusive OR

Expression:

Space Requirement: 1 line x 6 column Location Requirement: Middle, Right rail

Function:

When the input is ON, this instruction finds logical exclusive OR of A and B, and stores the result
in C.

Execution Condition:

Input

Operation

Output

OFF

No execution

OFF

ON

Execution

ON

Operand:

Coil or Bit

Register

Constant

Index

Name

X

Y B

S

T.

C.

M

X
W

Y
W

B
W

S
W

T C

D

I

J

K

M
W

A

Source

√ √

B

Source

√ √

C

AND

√ √

Example:

When B012 is ON, exclusive OR operation is executed for the data of D1000 and D0300, and the
result is stored in D1000.

If the data of D1000 is H5678 and D0300 is H4321, the result H1559 is stored in D1000.