Special instructions – Maple Systems MAPware-7000 User Manual
Page 20
![background image](/manuals/358875/20/background.png)
MAPware-7000 Ladder Logic Guide
12
1010-1041 rev. 00
Instruction Name
Symbol
Description
Execution
Time (μSec)
Upper Limit
Compares the current value in a register
A with a set value in B. If the current
value A is less than B, then A is stored in
result C. If A is greater than B, B is stored
into C.
2.3 μsec
Lower Limit
Compares the current value in a register
A with a set value in B. If the current
value A is greater than B, then A is stored
in result C. If A is less than B, B is stored
into C.
2.1 μsec
Maximum Value
Searches for the maximum value in a
table of registers (of size n), beginning
with register A, then stores the maximum
value into register B.
4.0 to 64.6
μsec
Minimum Value
Searches for the minimum value in a
table of registers (of size n), beginning
with register A, then stores the minimum
value into register B.
3.9 to 61.1
μsec
Average Value
Computes the mean average value of a
table of registers (of size n), beginning
with register A, then stores the result into
register B.
12.5 to 39.7
μsec
Function Generator
Finds f(x) for given x=A, and stores result
in C. The function f(x) is defined by
parameters stored in a table of registers
(of size 2n), beginning with register B.
5.2 to 68.8
μsec
Data Log Upload
Uploads data logger from attached USB
Special Instructions
These are instructions which include data processing functions, I/O instructions, and RAS.
Instruction Name
Symbol
Description
Execution
Time (μSec)
Device Set
Sets target coil address to ON.
1.1 μsec
Device Reset
Clears target coil address to OFF.
1.1 μsec